Plan Review Notes
Plan Review Notes For Permit 10100632
Permit Number 10100632
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-11-16 13:43:01319 CLEMATIS STREET, SUITE #100
 PERMIT #10100632
 REVIEW COMMENTS - FIRE
  
 SHEET A-4
  
 PROVIDE SCOPE OF FIRE SPRINKLER MODIFICATION. NOTE 50
 OR MORE SPRINKLERS REQUIRE THE SIGN AND SEAL OF A
 PROFESSIONAL ENGINEER. SEPARATE PLANS AND PERMIT
 REQUIRED FOR SPRINKLER WORK.
  
 PROVIDE SCOPE OF FIRE ALARM MODIFICATION. SEPARATE
 PLANS AND PERMIT REQUIRED FOR FIRE ALARM WORK.
  
 LOCATION OF EXIT SIGNS, EMERGENCY LIGHTS AND PORTABLE
 FIRE EXTINGUISHERS NOT SHOWN.
  
 PANIC/FIRE EXIT HARDWARE IS REQUIRED ON EXIT DOORS
 WHERE THE OCCUPANT LOAD EXCEEDS 100 PERSONS.
  
 IN BUILDINGS FULLY PROTECTED WITH AUTOMATIC SPRINKLERS,
 THE MINIMUM SEPARATION DISTANCE BETWEEN EXITS SHALL BE
 NOT LESS THAN ONE-THIRD THE LENGTH OF THE MAXIMUM
 OVERAL DIAGONAL DIMENSION OF BUILDING OR AREA BEING
 SERVED.
  
 SOUTH EXITS ARE OBSTRUCTED BY TABLES AND CHAIRS IF THEY
 ARE INTENDED TO BE USED AS EXITS. DOORS NOT INTENDED
 FOR EXIT USE SHALL BE MARKED AS "NOT AN EXIT."
  
 NO WHEELCHAIR SEATING HAS BEEN PROVIDED ON FURNITURE
 PLAN.
  
 PROVIDE THE ANTICIPATED AMOUNT (BOTTLES AND VOLUME) OF
 WINE THAT WILL BE PRESENT AT ANY TIME IN THIS
 OCCUPANCY.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6730