2010-11-16 18:35:171) SUBMIT MODEL NUMBERS OF NEW LIGHTING FIXTURES.
 2) SUBMIT LIGHTING DENSITIE CALCULATIONS AS PER
 13-415.ABC 2007 F.B.C.
 3) SHOW LOCATION OF EXISTING PANELS.
 4) DO NOT UNDERSTAND RISER DIAGRAM,PLEASE REDRAW
 SHOWING ORDER OF EQUIPMENT.
 5) SHOW SIZE OF MAIN FEEDERS FROM 600 AMP MAIN TO
 PANELS.
 6) PANEL SCHEDULE SHOWS PANEL B AS BEING 100 AMP BUS.
  