2010-11-19 16:55:18 | BUILDING PLAN REVIEW |
| PERMIT: 10100632 |
| ADD: 319 CLEMATIS ST 1ST FLOOR |
| CONT: WELLINGTON, EQUESTION |
| TEL: (561)951-6729 |
| |
| FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| |
| REVIEW |
| ACTION: DENIED |
| 1) SHEET A-4 INDICATES A BUILDING CODE ANALYSIS, PLANS |
| INDICATE IT TO BE A TYPE 5B, PLEASE SEE 2007 FBC-B |
| TABLE 503, THIS BEING A HIGH RISE PLEASE REVIEW TYPE |
| L-A AND L-B. DEPENDING ON THE BUILDING HEIGHT IIN |
| STORIES IT IS EITHER A I-A OR I-B. PLEASE CORRECT. |
| |
| 2) PLEASE REVIEW THE SCALE THE PLANS ARE DRAWN TO, THE |
| PLANS INDICATE 1/4 INCH BUT SCALE OUT TO BE 3/16 OF AN |
| INCH FOR ALL DOOR |
| WAYS. THIS WILL DRAMATICALLY EFFECT TRAVEL DISTANCES. |
| |
| 3) THE MAIN DINING ROOM DOES HAVE 2 EXITS THAT WILL |
| MEET THE 1/3RD THE DIAGONAL, BUT NOT THE REQUIREMENTS |
| OF FBC-B 1014.3(5) COMMON PATH OF TRAVEL. PLEASE |
| PROVIDE THE IDSTANCES FOR THE COMMON PATH OF TRAVEL |
| DISTANCES FROM THE MOST REMOTE POINT IN THE TENANT |
| SPACE . COMMON PATH OF TRAVEL IS MEASURED FROM THE MOST |
| REMOTE POINT IN A SPACE TO THE POINT IN THE EXIT PATH |
| WHERE AN OCCUPANT HAS ACCESS TO TWO REQUIRED EXITS IN |
| SEPERATE DIRECTIONS. |
| |
| 4) THE MAIN DINING ROOM REQUIRES TWO EXITS 1/3RD THE |
| DISTANCE APART, THE DOORWAYS ARE THERE BUT NOT THE |
| SECOND REQUIRED EXIT ACCESS, IT IS BLOCKED BY DINING |
| ROOM TABLES. FBC-B 1015.2 & 1005.1 MULTIPLE MEANS OF |
| EGRESS SHALL BE SIZED SUCH THAT THE LOSS OF ANY ONE |
| MEANS OF EGRESS SHALL NOT REDUCE THE AVAILABLE CAPACITY |
| TO LESS THAN 50 PERCENT OF THE REQUIRED CAPACITY. |
| |
| 5) THE PLANS DO NOT PROVIDE ANY FINISH INFORMATION FOR |
| FLOOR, WALL OR CEILING FINISHES PER FBC-B 803.1 & TABLE |
| 803.5. |
| |
| 6) THE PLANS ALSO WILL NEED TO SHOW COMPLIANCE WITH : |
| 11-5.2 COUNTERS AND BARS. WHERE FOOD OR DRINK IS SERVED |
| AT COUNTERS EXCEEDING 34 INCHES (865 MM) IN HEIGHT FOR |
| CONSUMPTION BY CUSTOMERS SEATED ON STOOLS OR STANDING |
| AT THE COUNTER, A PORTION OF THE MAIN COUNTER WHICH IS |
| 60 INCHES (1525 MM) IN LENGTH MINIMUM SHALL BE PROVIDED |
| IN COMPLIANCE WITH SECTION 11-4.32 OR SERVICE SHALL BE |
| AVAILABLE AT ACCESSIBLE TABLES WITHIN THE SAME AREA. |
| |
| 11-5.3 ACCESS AISLES. ALL ACCESSIBLE FIXED TABLES SHALL |
| BE ACCESSIBLE BY MEANS OF AN ACCESS AISLE AT LEAST 36 |
| INCHES (915 MM) CLEAR BETWEEN PARALLEL EDGES OF TABLES |
| OR BETWEEN A WALL AND THE TABLE EDGES. |
| |
| 7) NEITHER A-4 OR E-1 PROVIDE FOR COMPLIANCE WITH FBC-B |
| 1006.1.1 MEANS OF EGRESS ILLUMINATION. |
| |
| A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A |
| RESULT OF THE ADDITIONAL INFORMATION REQUESTED |
| ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF |
| THIS REVIEW. |
| |
| INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |