2011-01-19 07:58:192007 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 1) THE PLUMBING RISER DIAGRAM ON A3 ONLY SHOWS ONE OF
 THE TWO LAVATORIES LOCATED IN THE MASTER BATHROOM.
 PLEASE REVISE THE DIAGRAM TO SHOW HOW THE SECOND
 LAVATORY IS CONNECTED TO THE BUILDING DRAIN AND HOW IT
 WILL BE VENTED.
  
 2) ON A3 THE VENT TO ROOF FOR THE WASHING MACHINE DRAIN
 IS SPECIFIED AS 2" ON THE PLUMBING RISER DIAGRAM AND 3"
 ON THE FLOOR PLAN. PLEASE COORDINATE THE VENT SIZE.
  
 3) ON A7 IN THE BUILDER NOTES AT THE BOTTOM OF THE
 ELECTRICAL SYMBOL LEGEND THERE IS A NOTE THAT STATES
 ALL PLUMBING SHALL COMPLY WITH THE 2004 FL PLUMBING
 CODE. PLEASE UPDATE THIS NOTE TO THE 2007 FL PLUMBING
 CODE.
  