Plan Review Notes For Permit 10100534 |
Permit Number |
10100534 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2011-01-19 15:53:40 | 2007 FBC W/2009 REVISIONS | | | | DENIED BY BUILDING | | | | 1) THE STRUCTURE IS LOCATED IN EXPOSURE 'C' PER 2007 | | FBC R301.2.1.4.3. PLEASE REVISE THE PLANS AND COMPONENT | | AND CLADDING PRESSURES ACCORDINGLY. (PREVIOUS COMMENT) | | THE COMPONENT AND CLADDING PRESSURES IN THE TABLE ON | | SHEET A2 HAVE NOT BEEN INCREASED BY THE HEIGHT AND | | EXPOSURE ADJUSTMENT COEFFICIENTS IN TABLE R301.2(3) FOR | | EXPOSURE C. | | | | 2) THE PRODUCT REVIEW AFFIDAVIT FROM THE P.E. WILL NEED | | TO BE REVISED TO INCLUDE THE FIXED GLASS TRANSOM WINDOW | | AND THE INCREASED COMPONENT AND CLADDING PRESSURES. | | | | 3) THE INSTALLATION SCHEDULE FOR THE STORM PANELS | | REQUESTED IN THE FIRST REVIEW IS INCOMPLETE. PLEASE | | SPECIFY THE WALL PRESSURES AND SHUTTER SPANS. THE GLASS | | SEPARATION IS NOT REQUIRED AS LONG AS THE SPAN | | LIMITATIONS IN THE PRODUCT APPROVAL ARE FOLLOWED PER | | THE PRODUCT APPROVAL. THE SUBSTRATE SPECIFIED ON THE | | SCHEDULE IS CBS. THE ANCHOR SPACING TABLES IN THE | | PRODUCT APPROVAL ARE FOR CONCRETE OR CONCRETE BLOCK. | | PLEASE SPECIFY WHICH ONE OF THESE SUBSTRATE TYPES THE | | ANCHORS WILL BE INSTALLED INTO. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|