2011-01-19 15:53:402007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) THE STRUCTURE IS LOCATED IN EXPOSURE 'C' PER 2007
 FBC R301.2.1.4.3. PLEASE REVISE THE PLANS AND COMPONENT
 AND CLADDING PRESSURES ACCORDINGLY. (PREVIOUS COMMENT)
 THE COMPONENT AND CLADDING PRESSURES IN THE TABLE ON
 SHEET A2 HAVE NOT BEEN INCREASED BY THE HEIGHT AND
 EXPOSURE ADJUSTMENT COEFFICIENTS IN TABLE R301.2(3) FOR
 EXPOSURE C.
  
 2) THE PRODUCT REVIEW AFFIDAVIT FROM THE P.E. WILL NEED
 TO BE REVISED TO INCLUDE THE FIXED GLASS TRANSOM WINDOW
 AND THE INCREASED COMPONENT AND CLADDING PRESSURES.
  
 3) THE INSTALLATION SCHEDULE FOR THE STORM PANELS
 REQUESTED IN THE FIRST REVIEW IS INCOMPLETE. PLEASE
 SPECIFY THE WALL PRESSURES AND SHUTTER SPANS. THE GLASS
 SEPARATION IS NOT REQUIRED AS LONG AS THE SPAN
 LIMITATIONS IN THE PRODUCT APPROVAL ARE FOLLOWED PER
 THE PRODUCT APPROVAL. THE SUBSTRATE SPECIFIED ON THE
 SCHEDULE IS CBS. THE ANCHOR SPACING TABLES IN THE
 PRODUCT APPROVAL ARE FOR CONCRETE OR CONCRETE BLOCK.
 PLEASE SPECIFY WHICH ONE OF THESE SUBSTRATE TYPES THE
 ANCHORS WILL BE INSTALLED INTO.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW