Plan Review Notes For Permit 10100534 |
Permit Number |
10100534 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-11-02 09:52:56 | 2007 FBC W/2009 REVISIONS | | | | DENIED BY PLUMBING | | | | 1) THE PLUMBING RISER DIAGRAM ON A3 IS MISSING THE | | MASTER BATH SHOWER. PLEASE CORRECT. | | | | 2) THE WET VENT FOR BATH #2 DOES NOT COMPLY WITH FBCR | | P3108.2. IN HORIZONTAL WET-VENT SYSTEMS, NOT MORE THAN | | ONE WET-VENTED FIXTURE SHALL DISCHARGE UPSTREAM OF THE | | DRY-VENTED FIXTURE DRAIN CONNECTION. | | | | 3) THE TUB IN BATH #2 IS INCORRECTLY LABELED AS A | | SHOWER. PLEASE CORRECT. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|