Plan Review Notes
Plan Review Notes For Permit 10100534
Permit Number 10100534
Review Stop E
Sequence Number 1
Notes
Date Text
2010-11-03 09:50:032007 FBC W/2009 REVISIONS
 2008 NEC
  
 ELECTRICAL REVIEW DENIED
  
 1) THE NAME AND LICENSE NUMBER OF THE PERSON
 RESPONSIBLE FOR THE ELECTRICAL DESIGN IS REQUIRED TO BE
 ON THE DRAWINGS. FS 471.003
  
 2) THE PLANS DO NOT COMPLY WITH 2008 NEC 210.52 FOR
 REQUIRED RECEPTACLE SPACING.
  
 3) SHOW COMPLIANCE WITH NEC 422.31 AND 422.32 FOR
 DISCONNECTING MEANS AT A/C COMPRESSOR AND OTHER MOTOR
 DRIVEN APPLIANCES OR PERMANENTLY CONNECTED APPLIANCES.
  
 4) SHOW COMPLIANCE WITH NEC 406.11 FOR TAMPER-RESISTANT
 RECEPTACLES.
  
 5) SHOW COMPLIANCE WITH NEC 210.12 (B) FOR ARC-FAULT
 CIRCUIT-INTERRUPTER PROTECTION IN FAMILY ROOMS, DINING
 ROOMS, LIVING ROOMS, BEDROOMS, CLOSETS, HALLS AND OTHER
 SIMILAR ROOMS OR AREAS.
  
 6) NEC 210.8 REQUIRES ALL 125 -VOLT, SINGLE PHASE, 15-
 AND 20- AMPERE RECEPTACLES INSTALLED IN GARAGES TO HAVE
 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION. THE
 RECEPTACLE FOR THE GARAGE DOOR OPENER IS REQUIRED TO
 COMPLY.
  
 7) SHOW COMPLIANCE WITH FBC R313.4 WHICH REQUIRES
 CARBON MONOXIDE ALARMS WITHIN 10 FEET OF EACH ROOM USED
 FOR SLEEPING PURPOSES.
  
 8) A PANEL SCHEDULE IN COMPLIANCE WITH NEC 408.4 IS
 REQUIRED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]