2010-11-17 13:29:57 | 2007 FBC W/2009 REVISIONS |
| |
| DENIED BY BUILDING |
| |
| 1) THE STRUCTURE IS LOCATED IN EXPOSURE 'C' PER 2007 |
| FBC R301.2.1.4.3. PLEASE REVISE THE PLANS AND COMPONENT |
| AND CLADDING PRESSURES ACCORDINGLY. |
| |
| 2) PLEASE REVISE THE DESIGN INFORMATION ON SHEET A2 TO |
| REFLECT ASCE 7-05 AND EXPOSURE C. |
| |
| 3) PLEASE REVISE THE PRESSURES IN THE TABLE ON A2 AND |
| UPDATE THE REFERENCE TO 2004 FBC TABLE 1609.6B TO 2007 |
| FBCR TABLE R301.2(2). |
| |
| 4) SUBMIT TWO COPIES OF A ROOF FRAMING AND PERMANENT |
| BRACING PLAN SPECIFYING THE ROOF TO WALL CONNECTIONS |
| FROM THE DESIGNER OF RECORD FOR THE STRUCTURE AND |
| SIGNED AND SEALED BY HIM. |
| |
| 5) UPDATE THE MASONRY NOTES ON A3 FROM SBCCI TO FBC AND |
| ACI 530 AND 531 FROM THE 1995 TO THE 2005 EDITION AS |
| REFERENCED BY 2007 FBC CHAPTER 43. |
| |
| 6) THE PRODUCT APPROVAL INSTALLATION INSTRUCTIONS FOR |
| THE SINGLE HUNG WINDOWS REQUIRES 2X BUCKS AND THE PLANS |
| SPECIFY 1X BUCKS. PLEASE CORRECT. |
| |
| 7) THE MULLION PRODUCT APPROVAL SUBMITTED IS FOR |
| HORIZONTAL APPLICATION TO MULL TRANSOMS OVER WINDOWS. |
| THE PLANS DO NOT SHOW ANY WINDOWS WITH TRANSOMS ABOVE |
| THEM. SUBMIT PRODUCT APPROVALS FOR VERTICAL ORIENTATION |
| BETWEEN WINDOWS. |
| |
| 8) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE FIXED |
| TRANSOM WINDOW ABOVE THE DOUBLE ENTRY DOORS. |
| |
| 9) SPECIFY THE SIZE OF THE TRANSOM WINDOW ABOVE THE |
| DOUBLE ENTRY DOORS ON THE PLANS. |
| |
| 10) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE |
| STRUCTURAL MULLION BETWEEN THE ENTRY DOORS AND THE |
| TRANSOM WINDOW ABOVE OR PROVIDE A DETAIL IF A POURED |
| LINTEL OR STEEL BEAM IS USED. |
| |
| 11) SUBMIT 2 COPIES OF AN INSTALLATION SCHEDULE AND KEY |
| PLAN FOR THE STORM PANELS. SPECIFY THE CONN TYPE, |
| SUBSTRATE, ANCHOR TYPE, ANCHOR SPACING, PANEL SPANS, |
| ETC ON THE SCHEDULE. |
| THE SCHEDULE FOR INSTALLATION OF OPENING PROTECTIVE |
| DEVICES IS AVAILABLE ON THE CONSTRUCTION SERVICES |
| WEBSITE UNDER PERMIT FORMS. |
| HTTP://WWW.WPB.ORG/CONSTRUCTION/PERMITS_FORMS.PHP |
| |
| 12) SUBMIT PRODUCT APPROVALS FOR THE TRUSS ANCHORS, |
| CONNECTORS AND STRAPS OR LIST THERE FL#S OR NOAS ON THE |
| PLANS. |
| |