Plan Review Notes
Plan Review Notes For Permit 10100467
Permit Number 10100467
Review Stop B
Sequence Number 1
Notes
Date Text
2010-10-22 12:24:24****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. THE LETTER REQUESTING A FEE REDUCTION AND THE
 ESTIMATE PROVIDED MAKE REFERENCE TO AWNINGS INSTALLED
 AT 368 CRANESNEST. PROVIDE A COST BREAKDOWN AND THE
 PERMIT NUMBER FOR THE PERMITTED AWNINGS REFERRED TO IN
 THE LETTER. I WAS UNABLE TO LOCATE AN AWNING PERMIT FOR
 368 CRANESNEST. VALUE OF IMPROVEMENT IS NEEDED TO
 DETERMINE PERMIT FEES.
  
 2. PROVIDE AN ELEVATION WHICH SHOWS HEIGHT OF
 INSTALLATION AND HEIGHT AT LOWEST PART OF AWNING,
 FBC3105.1.
  
 3. PROVIDE DOCUMENTATION TO SHOW THAT THE FABRIC
 PROPOSED COMPLIES WITH FBC3105.3, NFPA701.
  
 4. PROVIDE A STRUCTURAL DETAIL WHICH SHOWS COMPLIANCE
 WITH FBC3105.4, WIND RESISTANCE.
  
 5. IF FABRIC IS TO BE RETRACTED IN THE ANTICIPATION OF
 HIGH WINDS, PROVIDE A LETTER, OR CONTRACTORS FORM,
 SIGNED BY THE OWNER (NOT THE TENANT) TO ACKNOWLEDGE
 THEIR RESPONSIBILITY TO HAVE THE AWNING COVER
 REMOVED/RETRACTED PRIOR TO ANY WIND EVENT WITH
 PROJECTED WIND SPEEDS OF 75 MPH OR GREATER. THE
 LETTER/FORM MUST BE SIGNED BY THE OWNER BUT IT NEED NOT
 BE NOTARIZED.
  
 6. REVISE THE SITE PLAN TO SHOW PROPOSED AWNING SIZES.
  
 7. REGARDING THE LETTER REQUESTING A FEE REDUCTION,
 THIS HAS BEEN DENIED BY THE BUILDING OFFICIAL DUE TO
 THE REQUIREMENT OF FBC 108.4, CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC AS A LICENSED CONTRACTOR
 PERFORMED THE WORK.
  
  