Plan Review Notes For Permit 10100399 |
Permit Number |
10100399 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2010-11-04 08:17:39 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | COMMENTS FROM PREVIOUS LIST: | | | | 1. DESIGN PRESSURES TO BE SPECIFIED BY A DESIGN | | PROFESSIONAL, FS471, FBC1609, ASCE7-05. | | | | A LETTER WAS SUBMITTED WHICH STATED THAT THE ATTACHED | | DOORS MEET OR EXCEED PRESSURES FOR ZONE 5. PLEASE | | REVISE THE LETTER TO SPECIFY THE PRODUCT REVIEWED BY | | THE ENGINEER AS NOTHING WAS ATTACHED TO THE LETTER. IF | | ENGINEER PRFERS TO SPECIFY PRODUCTS IN LIEU OF | | SPECIFYING DESIGN PRESSURES, A REFERENCE TO PRODUCT | | APPROVAL NUMBER (AND SPECIFIC PRODUCT WITHIN THE | | PRODUCT APPROVAL) IS REQUIRED. | | | | 2. PROVIDE A PLAN SHOWING DOOR LOCATION. THE DESIGN | | PROFESSIONAL IS TO DETERMINE WHETHER DOORS ARE LOCATED | | IN ZONE 4 OR ZONE 5. | | | | NO PLAN PROVIDED. SEE ALSO FIRE COMMENTS. | | | | |
|