Plan Review Notes
Plan Review Notes For Permit 10100399
Permit Number 10100399
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-11-04 10:29:42525 SOUTH FLAGLER DRIVE
 PERMIT #10100399
  
 REVIEW COMMENTS: FIRE
  
 1) PROVIDE FLOOR PLAN INDICATING WHICH DOORS WILL BE
 REPLACED.
  
 2) PROVIDE DOOR CLOSERS AND LISTED FIRE EXIT HARDWARE
 FOR RATED DOORS.
  
 3) PROVIDE DIRECTION OF DOOR SWING OF ALL EXIT DOORS.
  
 4) PROVIDE UL FIRE RESISTANCE RATING OF PROPOSED DOORS.
 APPLICATION STATES DOORS BE RATED AT 90- MINUTES.
  
 5) TRANSOM OR WINDOWS ARE REQUIRED TO BE FIRE RATED ON
 FIRE RATED DOORS.
  
 6) IF ELECTRIC HARDWARE OR CONTROLED ACCESS IS INTENDED
 TO BE USED PLEASE PROVIDE THIS INFORMATION.
  
 WJOLIN, DDANIELS
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 561 805-6730
  
  
  
  


Account Summary | Usage Policy | Privacy Policy