Plan Review Notes For Permit 10100397 |
Permit Number |
10100397 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2010-11-15 13:41:53 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | COMMENTS FROM PREVIOUS LIST: | | | | 1. ADDRESSED. | | | | 2. SEE BUILDING PROVISO #2, FAC9B72, PRODUCT APPROVALS | | REVIEWED BY DESIGNER OF RECORD REQUIRED FOR ALL | | COMPONENTS AND CLADDING. PLEASE HAVE THE ROOF PRODUCT | | APPROVALS REVIEWED PRIOR TO SUBMISSION. | | | | 2ND REVIEW, PLEASE HAVE DESIGNER OF RECORD REVIEW | | PRODUCT APPROVAL. | | | | 3. PRIOR TO INSTALLATION, INVESTIGATE AND ADDRESS ANY | | POTENTIAL ISSUES WHICH MAY ARISE FROM DISSIMILAR METALS | | ON THE ROOF (METAL ROOF, COPPER FLASHING, ALUMINUM | | GUTTERS), R904.2. | | | | 4. BUILDING PROVISO #6, ENGINEER TO PROVIDE A LETTER OR | | REVISE THE PLAN TO CONFIRM THAT THE DESIGN CONFORMS TO | | THE REQUIREMENT OF FBC R301.2.1.4.3(2), "ROOF SHEATHING | | UPLIFT AND ROOF-TO-WALL UPLIFT LOADS SHALL BE INCREASED | | BY 20 PERCENT." PLEASE NOTE THAT SOME OF THE UPLIFT | | ANCHORS DO NOT APPEAR TO BE INCREASED ON THE PLAN | | SUBMITTED. THIS ITEM MUST BE ADDRESSED PRIOR TO | | INSTALLATION OF ROOF FRAMING COMPONENTS AND PRIOR TO | | ISSUANCE OF ROOF PERMIT. | | | | 5. UNDERLAYMENT PRODUCT APPROVAL SUBMITTED DOES NOT | | INCLUDE THE INSTALLATION INSTRUCTIONS/EVALUATION | | REPORT, FAC9B72. | | | | 6. ADDRESSED. | | |
|