2010-11-15 13:41:53****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 COMMENTS FROM PREVIOUS LIST:
  
 1. ADDRESSED.
  
 2. SEE BUILDING PROVISO #2, FAC9B72, PRODUCT APPROVALS
 REVIEWED BY DESIGNER OF RECORD REQUIRED FOR ALL
 COMPONENTS AND CLADDING. PLEASE HAVE THE ROOF PRODUCT
 APPROVALS REVIEWED PRIOR TO SUBMISSION.
  
 2ND REVIEW, PLEASE HAVE DESIGNER OF RECORD REVIEW
 PRODUCT APPROVAL.
  
 3. PRIOR TO INSTALLATION, INVESTIGATE AND ADDRESS ANY
 POTENTIAL ISSUES WHICH MAY ARISE FROM DISSIMILAR METALS
 ON THE ROOF (METAL ROOF, COPPER FLASHING, ALUMINUM
 GUTTERS), R904.2.
  
 4. BUILDING PROVISO #6, ENGINEER TO PROVIDE A LETTER OR
 REVISE THE PLAN TO CONFIRM THAT THE DESIGN CONFORMS TO
 THE REQUIREMENT OF FBC R301.2.1.4.3(2), "ROOF SHEATHING
 UPLIFT AND ROOF-TO-WALL UPLIFT LOADS SHALL BE INCREASED
 BY 20 PERCENT." PLEASE NOTE THAT SOME OF THE UPLIFT
 ANCHORS DO NOT APPEAR TO BE INCREASED ON THE PLAN
 SUBMITTED. THIS ITEM MUST BE ADDRESSED PRIOR TO
 INSTALLATION OF ROOF FRAMING COMPONENTS AND PRIOR TO
 ISSUANCE OF ROOF PERMIT.
  
 5. UNDERLAYMENT PRODUCT APPROVAL SUBMITTED DOES NOT
 INCLUDE THE INSTALLATION INSTRUCTIONS/EVALUATION
 REPORT, FAC9B72.
  
 6. ADDRESSED.
  