2010-11-08 10:14:04 | ****CORRECTIONS**** |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| FBC FLORIDA BUILDING CODE 2007 |
| FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| |
| 1. THE METAL ROOF PRODUCT SUBMITTED HAS A DESIGN |
| PRESSURE LIMITATION OF -30PSF. SEE SHEET S-5, -56.5 |
| REQUIRED FOR ZONE 3, -48.4 REQUIRED FOR ZONE 2. |
| |
| 2. SEE BUILDING PROVISO #2, FAC9B72, PRODUCT APPROVALS |
| REVIEWED BY DESIGNER OF RECORD REQUIRED FOR ALL |
| COMPONENTS AND CLADDING. PLEASE HAVE THE ROOF PRODUCT |
| APPROVALS REVIEWED PRIOR TO SUBMISSION. |
| |
| 3. PRIOR TO INSTALLATION, INVESTIGATE AND ADDRESS ANY |
| POTENTIAL ISSUES WHICH MAY ARISE FROM DISSIMILAR METALS |
| ON THE ROOF (METAL ROOF, COPPER FLASHING, ALUMINUM |
| GUTTERS), R904.2. |
| |
| 4. BUILDING PROVISO #6, ENGINEER TO PROVIDE A LETTER OR |
| REVISE THE PLAN TO CONFIRM THAT THE DESIGN CONFORMS TO |
| THE REQUIREMENT OF FBC R301.2.1.4.3(2), "ROOF SHEATHING |
| UPLIFT AND ROOF-TO-WALL UPLIFT LOADS SHALL BE INCREASED |
| BY 20 PERCENT." PLEASE NOTE THAT SOME OF THE UPLIFT |
| ANCHORS DO NOT APPEAR TO BE INCREASED ON THE PLAN |
| SUBMITTED. THIS ITEM MUST BE ADDRESSED PRIOR TO |
| INSTALLATION OF ROOF FRAMING COMPONENTS AND PRIOR TO |
| ISSUANCE OF ROOF PERMIT. |
| |
| 5. UNDERLAYMENT PRODUCT APPROVAL SUBMITTED DOES NOT |
| INCLUDE THE INSTALLATION INSTRUCTIONS/EVALUATION |
| REPORT, FAC9B72. |
| |
| 6. THE ROOF METAL PRODUCT APPROVAL PROVIDED IS |
| "VALIDATED," SHOULD BE "APPROVED." PLEASE PROVIDE |
| CURRENT COVER SHEETS FOR ANY FLORIDA STATE PRODUCT |
| APPROVALS SUBMITTED, FAC9B72, WWW.FLORIDABUILDING.ORG. |