Plan Review Notes For Permit 10100303 |
Permit Number |
10100303 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2010-11-29 09:39:57 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW SECOND | | CHECKLIST. | | 2007 FBC WITH 2007 REVISIONS. | | | | 1- PROVIDE ENGINEERING FOR ROOF TO WALL CONNECTIONS AS | | REQUIRED BY SEC. 611.8 FBC 2007 EXISTING BUILDING CODE | | OR PROVIDE CURRENT PROPERTY APPRAISAL (BY LICENSED | | PROPERTY APPRAISER) SHOWING THAT THE STRUCTURE ALONE | | WITHOUT THE DETACHED GARAGE IS WORTH LESS THAN $300.00. | | | | 2- RAS 117 CALCULATIONS; ENGINEER TO REVISE NAIL | | SPACING FOR ZONE 1. NAIL SPACING FOR ZONE 1 SHALL BE | | THE NAIL SPACING SPECIFIED ON THE NOA SUBMITTED. SEE | | SEC. 8.1 OF RAS 117. | | | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|