Plan Review Notes For Permit 10100303 |
Permit Number |
10100303 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-10-14 14:12:44 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. | | 2007 FBC WITH 2009 REVISIONS. | | | | 1- PROVIDE ENGINEERING REPORT SHOWING COMPLIANCE WITH | | THE ROOF TO WALL CONNECTIONS AS REQUIRED BY SEC. 611.8 | | OF 2007 FBC-EXISTING BUILDING. | | | | 2- FLAT ROOF PRODUCT APPROVAL: | | A) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR | | NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS | | REQUIRED BY GENERAL LIMITATION #7 ON NOA 08-0226.06 | | SUBMITTED. SEE GENERAL LIMITATIONS ON LAST PAGE OF NOA | | SUBMITTED. | | | | B) DESIGN PROFESSIONAL DOING THE RAS 117 CALCULATIONS | | TO TAKE INTO CONSIDERATION THAT ACCORDING TO 2009 | | REVISIONS SEC. R301.2.1.4.3, THIS BUILDING IS LOCATED | | IN EXPOSURE "C". | | | | 3- A) SPECIFIED HOW IS THE ROOF TILE GOING TO BE | | FASTENED TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES | | OF SEC. R301 OF 2007 FLORIDA RESIDENTIAL CODE. | | | | B) IF USING ADHESIVE, THEN PROVIDE PRODUCT APPROVAL. | | SEE TILE NOA FOR LISTED ADHESIVES. | | | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 | | |
|