2010-10-22 10:20:18 | *******PROVISO***** |
| |
| 504.6 REQUIREMENTS FOR DISCHARGE PIPING. THE DISCHARGE |
| PIPING SERVING A PRESSURE RELIEF VALVE, TEMPERATURE |
| RELIEF VALVE OR COMBINATION THEREOF SHALL: |
| |
| 1. NOT BE DIRECTLY CONNECTED TO THE DRAINAGE SYSTEM. |
| 2. DISCHARGE THROUGH AN AIR GAP LOCATED IN THE SAME |
| ROOM AS THE WATER HEATER. |
| 3. NOT BE SMALLER THAN THE DIAMETER OF THE OUTLET OF |
| THE VALVE SERVED AND SHALL DISCHARGE FULL SIZE TO THE |
| AIR GAP. |
| 4. SERVE A SINGLE RELIEF DEVICE AND SHALL NOT CONNECT |
| TO PIPING SERVING ANY OTHER RELIEF DEVICE OR EQUIPMENT. |
| 5. DISCHARGE TO THE FLOOR, TO THE WATER HEATER PAN, TO |
| AN INDIRECT WASTE RECEPTOR OR TO THE OUTDOORS. WHERE |
| DISCHARGING TO THE OUTDOORS IN AREAS SUBJECT TO |
| FREEZING, DISCHARGE PIPING SHALL BE FIRST PIPED TO AN |
| INDIRECT WASTE RECEPTOR THROUGH AN AIR GAP LOCATED IN A |
| CONDITIONED AREA. |
| 6. DISCHARGE IN A MANNER THAT DOES NOT CAUSE PERSONAL |
| INJURY OR STRUCTURAL DAMAGE. |
| 7. DISCHARGE TO A TERMINATION POINT THAT IS READILY |
| OBSERVABLE BY THE BUILDING OCCUPANTS. |
| 8. NOT BE TRAPPED. |
| 9. BE INSTALLED SO AS TO FLOW BY GRAVITY. |
| 10. NOT TERMINATE MORE THAN 6 INCHES (152 MM) ABOVE THE |
| FLOOR OR WASTE RECEPTOR. |
| 11. NOT HAVE A THREADED CONNECTION AT THE END OF SUCH |
| PIPING. |
| 12. NOT HAVE VALVES OR TEE FITTINGS. |
| 13. BE CONSTRUCTED OF THOSE MATERIALS LISTED IN SECTION |
| 605.4 OR MATERIALS TESTED, RATED AND APPROVED FOR SUCH |
| USE IN ACCORDANCE WITH ASME A112.4.1. |
| |