Plan Review Notes
Plan Review Notes For Permit 10100221
Permit Number 10100221
Review Stop B
Sequence Number 1
Notes
Date Text
2010-10-12 14:24:18RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- ACCORDING TO THE MIAMI-DADE WEBSITE NOA 06-0410.06
 FILE IS CLOSED. NEED TO PROVIDE CURRENT NOA.
  
 2- A) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS
 FOR NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION #7. SEE GENERAL
 LIMITATION #7 ON LAST PAGE OF NOA SUBMITTED.
  
 B) DESIGN PROFESSIONAL DOING THE RAS 117 CALCULATIONS
 TO TAKE INTO CONSIDERATION THAT ACCORDING TO THE 2009
 REVISIONS SEC. R301.2.1.4.3 THIS BUILDING IS LOCATED ON
 EXPOSURE "C".
  
 ***NOTE: APPROVED ASSEMBLIES LIMITED BY GENERAL
 LIMITATION #9 CAN'T BE USED IN THIS BUILDING BECAUSE
 THE DESIGN PRESSURES CAN'T NOT BE ENHANCED. SEE GENERAL
 LMITATION #9 ON LAST PAGE OF NOA SUBMITTED.
  
 3- PERMIT VALUATION DECLARED IN THE PERMIT VALUATION IS
 TOO LOW. SEC. 108.3 CITY AMENDMENTS TO FBC. VALUATION
 WAS UPDATED. THE PERMIT FEE BALANCE IS $122.99.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712