Plan Review Notes For Permit 10100163 |
Permit Number |
10100163 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2010-11-17 14:37:26 | ****PROVISO**** | | ****REVISION REQUIRED**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | 1. SEE FBC R CHAPTER 10; R1003, MASONRY CHIMNEYS AND | | FBC R1005, FACTORY BUILT CHIMNEYS, AND FBC R 1801.3.4. | | REVISE PLAN TO SHOW COMPLIANCE AND PROVIDE ANY | | ADDITIONAL SUPPLEMENTARY INFORMATION REQUIRED TO SHOW | | COMPLIANCE. PROVIDE A COMPLETE DETAIL OF THE CHIMNEY, | | ALL COMPONENTS AFFECTED. | | | | 2. PLANS ARE TITLED "REMODEL ADDITION." THIS PERMIT IS | | FOR FRAMING REPAIRS ONLY ON EXISTING AREAS, NO NEW | | INTERIOR OR EXTERIOR ROOF AREA. | | | | 3. PLANS SHOW ONLY CASEMENT WINDOWS. THE FIXED GLASS | | WINDOW PRODUCT APPROVALS HAVE BEEN REMOVED. SUBMIT AS A | | REVISION WITH REVISED PLAN IF FIXED GLASS IS PROPOSED. | | | | 5. FOR THE FLAT DECK ROOF, SPECIFY ENHANCED FASTENING | | FOR ZONES 2 AND 3, FBC R301. SEE RAS 117. | | |
|