2010-10-20 14:37:14FBC 2007 PLUMBING PLAN REVIEW #1
 DENIED:
  
 MED GAS
 1. NOT ENOUGH INFORMATION WAS FOUND FOR A REVIEW ON MED
 GAS. SHEETS P-2.0 & P-3.0 REFER TO SP PLANS- (WERE NOT
 FOUND)
  
 WATER HEATER
 1. SHEETS P-2.0 & P-3.0 SHOW RELIEF LINE FOR WATER
 HEATER TO OUTSIDE OF BLDG. 504.6 RELIEF DISCHARGE SHALL
 BE THROUGH AN AIR GAP IN THE SAME ROOM AS THE WATER
 HEATER (ALLOWED TO DISCHARGE INTO A HEATER PAN OR AIR
 GAP FITTING).
  
 SANITARY
 2. DENTAL EQUIPTMENT ROOM SHOWS NO DRAINAGE OR WATER
 FOR THE EQUIPTMENT.
  
 *****PROVISOS*****
  
 SHEET A-502
 FBC 11-4.24.2
 SINK COUNTER TOP TO BE A MAXIMUM OF 34" ABOVE FINISHED
 FLOOR.
 A CLEAR FLOOR SPACE OF 48" X 30" IS REQUIRED IN FRONT
 OF SINK.
  
 GRAB BARS ARE TO BE BETWEEN 33"- 36" A.F.F. TO CENTER.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692