Plan Review Notes For Permit 10100153 |
Permit Number |
10100153 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-10-20 14:37:14 | FBC 2007 PLUMBING PLAN REVIEW #1 | | DENIED: | | | | MED GAS | | 1. NOT ENOUGH INFORMATION WAS FOUND FOR A REVIEW ON MED | | GAS. SHEETS P-2.0 & P-3.0 REFER TO SP PLANS- (WERE NOT | | FOUND) | | | | WATER HEATER | | 1. SHEETS P-2.0 & P-3.0 SHOW RELIEF LINE FOR WATER | | HEATER TO OUTSIDE OF BLDG. 504.6 RELIEF DISCHARGE SHALL | | BE THROUGH AN AIR GAP IN THE SAME ROOM AS THE WATER | | HEATER (ALLOWED TO DISCHARGE INTO A HEATER PAN OR AIR | | GAP FITTING). | | | | SANITARY | | 2. DENTAL EQUIPTMENT ROOM SHOWS NO DRAINAGE OR WATER | | FOR THE EQUIPTMENT. | | | | *****PROVISOS***** | | | | SHEET A-502 | | FBC 11-4.24.2 | | SINK COUNTER TOP TO BE A MAXIMUM OF 34" ABOVE FINISHED | | FLOOR. | | A CLEAR FLOOR SPACE OF 48" X 30" IS REQUIRED IN FRONT | | OF SINK. | | | | GRAB BARS ARE TO BE BETWEEN 33"- 36" A.F.F. TO CENTER. | | | | REVIEW BY LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | (561) 805-6692 | | FAX (561) 653-2692 | | E-MAIL [email protected] | | | | |
|