Plan Review Notes For Permit 10100153 |
Permit Number |
10100153 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-10-22 09:46:19 | PLAN DENIED | | 1) PLEASE REFER TO SECTION 601.4 2007 FMC BALANCED | | RETURN AIR EXCEPTION # 3 KITCHEN AND DENTAL EQUIPMENT | | ROOM . | | 2) PLEASE REFER TO SECTION 606.2.1 2007 FMC SUPPLY AIR | | SYSTEM SEE EXCEPTION . | | 3) REFER TO SECTION 606.3 INSTALLATION | | 4) PLEASE REFER TO SECTION 602.2.1 MATERIALS EXPOSED | | WITHIN PLENUMS . CAN NOT USE WOOD DOORS ON THE A/C | | CLOSET | | 5) PLEASE PROVIDE A DETAIL ON THE PLANS FROM THE | | ENGINEER ON THE A/C STAND TIE DOWN TO THE ROOF. | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|