2010-10-18 13:19:02321-8TH STREET
 PERMIT NUMBER 10100153
 "ALTERATION/ REMODEL OF EXISTING 1 STORY STRUCTURE FOR
 DENTAL OFFICE"
  
  
 1. THE BUILDING ADDRESS DISPLAYED ON SHEET A-700 SHALL
 BE AT LEAST 6" HIGH AND AT LEAST 1" WIDE THAT CONTRASTS
 TO THE BACKGROUND THAT IT IS AFFIXED TO.
  
 2. NO EXIT SIGNS, EMERGENCY LIGHTS OF PORTABLE FIRE
 EXTINGUISHERS DISPLAYED ON THE PLANS.
  
 3. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 4. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS.
  
 5. THE BUILDING IS TO BE PLACARDED WITH A MALTESE CROSS
 WITH THE LETTER "R" SIGNIFYING WOODEN ROOF TRUSSES.
  
 6. PLEASE INDICATE INFORMATION RELATED TO THE TYPES OF
 MEDICAL GASES, (OXYGEN, NITROUS OXIDE, ETC.) THAT MAY
 BE PLANNED FOR THE FACILITY.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION