Plan Review Notes For Permit 10100056 |
Permit Number |
10100056 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-11-03 10:07:20 | 2406 FLORIDA AVENUE | | PERMIT #10100056 | | | | REVIEW COMMENTS - FIRE | | | | 1) PROVIDE NEW STAIR PER CHAPTER 7 OF THE FLORIDA FIRE | | PREVENTION CODE 2007 EDITION (NFPA 101- LIFE SAFETY | | CODE 2006 EDITION WITH FLORIDA AMENDMENTS). | | | | 2) STAIRS SHALL HAVE HANDRAILS ON BOTH SIDES PER | | 7.2.2.4.1.1 (FFPC - NFPA 101). | | | | 3) NEW HANDRAIL ENDS SHALL BE RETURNED TO THE WALL OR | | FLOOR OR SHALL TERMINATE AT NEWEL POSTS PER 7.2.2.4.4.9 | | (FFPC - NFPA 101). | | | | 4) OUTSIDE STAIRS AND LANDINGS SHALL BE DESIGNED TO | | MINIMIZE WATER ACCUMULATION OF THEIR SURFACES PER | | 7.2.2.6.5 (FFPC - NFPA 101). | | | | WESLEY JOLIN | | WEST PALM BEACH FIRE RESCUE | | FIRE & LIFE SAFETY PLAN REVIEW | | 561-805-6730 |
|