Plan Review Notes For Permit 10100056 |
Permit Number |
10100056 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-11-02 09:51:15 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | 1. PROVIDE A SITE PLAN SHOWING PROPOSED IMPROVEMENT | | LOCATION, FBC106. | | | | 2. PLEASE REVISE PLAN TO SHOW HOW THE PROPOSED | | IMPROVEMENT WILL AFFECT EXITING, FBC CH. 10, FBC CH. | | 11. STAIRS SHOWN, BUT NO INFORMATION PROVIDED REGARDING | | AREA SERVED, AND NO INFORMATION SHOWN REGARDING DEMO OR | | INSTALLATION OF NEW DOORS. INCLUDE ENOUGH INFORMATION | | REQUIRED TO DEMONSTRATE CODE COMPLIANCE. | | | | 3. SHOW DISTANCE FROM PROPOSED LANDING TO FINISHED | | FLOOR OF AREA WHICH THE PROPOSED STAIR WILL SERVE. | | | | 4. PROIVDE A DETAIL FOR THE GUARD/HAND RAIL, FBC 1012, | | 1012.5, 1013, 11-4.8.5. | | | | | | |
|