2011-01-03 15:07:55 | BUILDING REVIEW THIRD CHECKLIST. |
| 2007 FBC WITH 2009 REVISIONS. |
| |
| 1- FLAT ROOF PRODUCT APPROVAL SUBMITTED: |
| A) NOA 07-0730.03 SUBMITTED IS SUPERSEDED ALSO. GO TO |
| THE MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT NOA. |
| B) REVISE SIGNED & SEALED RAS 117 CALCULATIONS TO |
| REFERENCE UPDATED NOA. |
| |
| 2- ENGINEER TO REVIEW/APPROVE UPDATED FLAT ROOF PRODUCT |
| APPROVAL. SEC. 106.3.3 CITY AMENDMENTS. |
| |
| 3- PROVIDE FRAMING DETAILS FOR NEW ATTIC ACCESS. |
| REVISED SHEET S-2 SUBMITTED DOESN'T SHOW ANY DETAILS. |
| |
| 4- SHEET A2.3: |
| A) REVISE MODIFIED ROOFING SPECS ON PARAPET FLASHING |
| DETAIL. BASE SHEET NAILING SPACING SHOWN DOESN'T MATCH |
| RAS 117 CALCULATIONS. THIS DETAIL SPECIFIES DYNAFLEX |
| MEMBRANE. SEE PRODUCT APPROVAL SUBMITTED AND REVISE AS |
| REQUIRED. REVISE NOA SPECIFIED TO MATCH NEW UPDATED |
| NOA. SELECTED ASSEMBLY DOESN'T HAVE INSULATION. REVISE |
| AS REQUIRED. |
| |
| B) EXISTING ROOF: ROOF SLOPE WAS MODIFIED. PROVIDE |
| CALCULATIONS TO SHOW THAT ONLY ONE SCUPPER IS ADEQUATE |
| AND SHOW SECONDARY EMERGENCY SCUPPER. NOT REVISED. |
| EXISTING ROOF ONLY SHOWS ONE SCUPPER AND THERE ARE NO |
| EMERGENCY SCUPPERS SHOWN. ALSO, FLAT ROOF SPECS REFER |
| TO "JOHNS MANVILLE" ROOFING SYSTEM. SEE PRODUCT |
| APPROVAL SUBMITTED AND REVISE AS REQUIRED. |
| |
| 5- REVISE SHEET A3.2. DETAIL 12/A5 KEYED ON PARAPETS |
| AND HEADERS IS FOR WINDOW SILL DETAIL ON WOOD FRAMED |
| WALL. |
| SHEET A3.3 SUBMITTED ALSO SPECIFIES DETAIL 12/A5 ON |
| PARAPET WALL. REVISE AS REQUIRED. |
| |