Plan Review Notes For Permit 10090739 |
Permit Number |
10090739 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2010-12-07 17:01:50 | BUILDING REVIEW APPROVED WITH PROVISO: | | 1- FLAT ROOF PRODUCT APPROVAL SUBMITTED: | | A) NOA 07-0228.06 IS SUPERSEDED. NEED CURRENT NOA. | | B) IDENTIFY APPROVED ASSEMBLY TO BE USED. | | C) PROVIDE SIGNED & SEALED RAS 117 CALCULATIONS. | | | | 2- ENGINEER TO REVIEW/APPROVE NEW FLAT ROOF PRODUCT | | APPROVAL. SEC. 106.3.3 CITY AMENDMENTS. | | | | 3- PROVIDE FRAMING DETAILS FOR NEW ATTIC ACCESS. | | | | 4- SPECIFY HOW OBTAINING R6 INSULATION ON THE MASONRY | | WALL. SEE ENERGY CALCULATIONS. | | | | 5- SHEET A2.3: | | A) REVISE MODIFIED ROOFING SPECS ON PARAPET FLASHING | | DETAIL. SEE ITEM 1C ABOVE. | | B) EXISTING ROOF: ROOF SLOPE WAS MODIFIED. PROVIDE | | CALCULATIONS TO SHOW THAT ONLY ONE SCUPPER IS ADEQUATE | | AND SHOW SECONDARY EMERGENCY SCUPPER. | | | | 6- NEW ATTIC SPACE WAS CREATED ON SECOND FLOOR: | | A) SPECIFY CEILING HEIGHT. SEC. R305. | | B) PROVIDE FRAMING DETAILS/SPECIFICATION FOR NEW HUNG | | CEILING. SEC. 106.1.1 CITY AMENDMENTS TO FBC. | | | | 7- REVISE SHEET A3.2. DETAIL 12/A5 KEYED ON PARAPETS, | | LINTELS, HEADERS AND WINDOW SILLS IS FOR WINDOW SILL | | DETAIL ON WOOD FRAMED WALL. |
|