2010-12-07 17:01:50BUILDING REVIEW APPROVED WITH PROVISO:
 1- FLAT ROOF PRODUCT APPROVAL SUBMITTED:
 A) NOA 07-0228.06 IS SUPERSEDED. NEED CURRENT NOA.
 B) IDENTIFY APPROVED ASSEMBLY TO BE USED.
 C) PROVIDE SIGNED & SEALED RAS 117 CALCULATIONS.
  
 2- ENGINEER TO REVIEW/APPROVE NEW FLAT ROOF PRODUCT
 APPROVAL. SEC. 106.3.3 CITY AMENDMENTS.
  
 3- PROVIDE FRAMING DETAILS FOR NEW ATTIC ACCESS.
  
 4- SPECIFY HOW OBTAINING R6 INSULATION ON THE MASONRY
 WALL. SEE ENERGY CALCULATIONS.
  
 5- SHEET A2.3:
 A) REVISE MODIFIED ROOFING SPECS ON PARAPET FLASHING
 DETAIL. SEE ITEM 1C ABOVE.
 B) EXISTING ROOF: ROOF SLOPE WAS MODIFIED. PROVIDE
 CALCULATIONS TO SHOW THAT ONLY ONE SCUPPER IS ADEQUATE
 AND SHOW SECONDARY EMERGENCY SCUPPER.
  
 6- NEW ATTIC SPACE WAS CREATED ON SECOND FLOOR:
 A) SPECIFY CEILING HEIGHT. SEC. R305.
 B) PROVIDE FRAMING DETAILS/SPECIFICATION FOR NEW HUNG
 CEILING. SEC. 106.1.1 CITY AMENDMENTS TO FBC.
  
 7- REVISE SHEET A3.2. DETAIL 12/A5 KEYED ON PARAPETS,
 LINTELS, HEADERS AND WINDOW SILLS IS FOR WINDOW SILL
 DETAIL ON WOOD FRAMED WALL.