2010-10-15 15:23:58 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST. |
| 2007 FBC WITH 2009 REVISIONS. |
| |
| 1- ACCORDING TO 2009 REVISIONS SEC. R301.2.1.4.3 OF THE |
| 2007 FLORIDA RESIDENTIAL CODE THIS BUILDING IS LOCATED |
| ON EXPOSURE "C" NOT EXPOSURE "B". REVISE STRUCTURAL |
| DRAWINGS AS REQUIRED. ENGINEER NEEDS TO REVISE THE |
| DESIGN CRITERIA AND THE COMPONENTS AND CLADDING DESIGN |
| PRESSURES ON THE STRUCTURAL DRAWINGS. |
| |
| 2- ENGINEER NEEDS TO INCREASE 20% ON THE ROOF SHEATHING |
| AND ROOF-TO-WALL UPLIFT LOADS AS REQUIRED BY 2009 |
| REVISIONS SEC. R301.2.1.4.3(2). |
| |
| 3- BRING PLANS TO THE HISTORIC DEPARTMENT FOR HISTORIC |
| APPROVAL STAMP BEFORE SUBMITTING THEM TO THIS OFFICE. |
| |
| 4- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| DCA RULE 9B-72 FOR: |
| (A) SINGLE HUNG WINDOWS AS SHOWN ON PLANS. PRODUCT |
| APPROVAL SUBMITTED IS FOR FIXED WINDOWS. THERE ARE NOT |
| FIXED WINDOWS SHOWN ON PLANS. AND, NOA 08-1112.10 |
| SUBMITTED WAS SUPERSEDED BY MIAMI-DADE. |
| |
| (B) SLIDING WINDOWS AS SHOWN ON PLANS. |
| |
| (C) FLAT ROOF SYSTEM TO BE USED: (1 )NOA SPECIFIED ON |
| ROOF FRAMING PLAN IS NOT THE SAME NOA THAT WAS |
| SUBMITTED. AND, IT CAN'T BE USED BECAUSE IT WAS |
| SUPERSEDED BY MIAMI-DADE. REVISE PLANS AND PRODUCT |
| APPROVAL TO MATCH. SEE MIAMI-DADE WEBSITE FOR CURRENT |
| PRODUCT APPROVALS. |
| (2) CLEARLY IDENTIFY WHICH APPROVED ASSEMBLY IS GOING |
| TO BE USED. |
| (3) PROVIDE RAS 117 CALCULATIONS AS REQUIRED BY GENERAL |
| LIMITATION #7. IF NOA SUBMITTED REQUIRES SIGNED AND |
| SEALED RAS 117 CALCULATIONS, THEN PROVIDE SIGNED AND |
| SEALED CALCULATIONS. |
| (4) DESIGN PROFESSIONAL DOING THE RAS 117 CALCULATIONS |
| TO TAKE INTO CONSIDERATION THAT THIS BUILDING IS |
| LOCATED ON EXPOSURE "C". |
| (5) FLAT ROOF NOA 07-0730.03 SUBMITTED WAS SUPERSEDED |
| BY MIAMI-DADE. NEED TO PROVIDE CURRENT NOA. SEE |
| MIAMI-DADE WEBSITE. AND PROVIDE RAS 117 CALCULATIONS. |
| SEE ITEM (C)(3) ABOVE. |
| |
| (D) PRECAST LINTELS AS SPECIFIED ON PLANS. |
| |
| (E) SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON PLANS. |
| |
| (F) EXTERIOR DOORS AS SHOWN ON PLANS. |
| |
| 5- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. |
| |
| 6- PROVIDE WINDOW CUT SHEETS SHOWING THAT 36"X56" |
| SINGLE HUNG WINDOW MEET THE MIN. CLEAR OPENING REQUIRED |
| OPENING AREA TO BE 5.7 S.FS AS REQUIRED BY SEC. |
| R310.1.1 AND R310.1.2 OF 2007 FLORIDA RESIDENTIAL CODE. |
| |
| 7- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO |
| VERIFY IF IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS |
| AND COPY OF PAID RECEIPT IF FEES ARE DUE. |
| |
| 8- SPECIFY CARBON MONOXIDE ALARMS ON PLANS AS REQUIRED |
| BY 2009 REVISIONS SEC. R313.4 OF 2007 FLORIDA |
| RESIDENTIAL CODE. |
| |
| 9- REVISE OVERFLOW SCUPPERS SHOWN ON SHEET A2.3 TO |
| COMPLY WITH SEC. R903.4.1 OF 2007 FLORIDA RESIDENTIAL |
| CODE. REVISE LOCATION OF MAIN SCUPPERS AND OVERFLOW |
| SCUPPER IN RELATION TO THE ROOF FINISH. SEE SEC. R903.4 |
| AND R903.4.1. |
| |
| 10- SPECIFY ROOF VENTILATION AS REQUIRED BY SEC. R806. |
| |
| 11- CLARIFY HOW INSTALLING R-30 BUTT INSULATION ON ROOF |
| DECK. AS SHOWN ON WALL SECTIONS AND DETAILS ON SHEET |
| A3.2 AND A3.3. REVISE AS REQUIRED. |
| |
| 12- REVISE STUCCO THICKNESS ON WOOD FRAMED WALLS NEED |
| 7/8" MIN. THICKNESS. SEE TABLE R702.1(1). REVISE ALL |
| WALL SECTIONS AND WALL LEGEND SPECIFICATIONS. |
| |
| 13- PROPOSED 2ND FLOOR PLAN ON SHEET A2.1 SHOWS 2'X3' |
| ATTIC ACCESS. THIS IS A FLAT ROOF. CLARIFY/REVISE AS |
| REQUIRED. |
| |
| 14- PARTIAL SECOND FLOOR PLAN ON SHEET S2 SHOWS BEAMS |
| RUNNING THRU CHASE OF EXISTING CHIMNEY. PROVIDE DETAILS |
| AND SPECIFICATIONS SHOWING COMPLIANCE WITH SEC |
| R1001.11. AND, THE FIREBLOCKING AND DRAFSTOPPPING |
| REQUIREMENTS. |
| |
| 15- REVISE ALL WALL SECTIONS AND WALL SCHEDULE |
| SPECIFICATIONS TO SPECIFY 2 LAYERS OF WATER RESISTANT |
| BARRIERS AS REQUIRED BY SEC. R703.6.3. |
| |
| 16- ENERGY CALCULATIONS: |
| A) ITEM #8 IS MISSING THE COMMON FLOOR. THIS IS A 2 |
| STORY ADDITION. |
| B) CLARIFY HOW OBTAINING R6 INSULATION ON THE MASONRY |
| WALL. AND, COORDINATE WITH INFORMATION SHOWN ON PLANS. |
| C) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. |
| D) COMPLETE ALL THE INFORMATION ON TOP OF THE FORM. |
| E) COORDINATE R VALUE SHOWN ON ITEM #9(2) WITH |
| INFORMATION SHOWN ON PLANS. |
| F) REVISE ITEM #10. THERE IS NOT ATTIC ON THIS HOUSE. |
| SEE PLANS. |
| G) COMPLETE ALL THE INFORMATION ON TABLES 11B-1 AND |
| 11B-2 ON SHEET 2. |
| |
| 17- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| FLORIDA STATUTE. |
| ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK |
| UP. |
| |