Plan Review Notes For Permit 10090717 |
Permit Number |
10090717 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-09-27 13:27:52 | RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST. | | 2007 FBC WITH 2009 REVISIONS. | | | | 1- PROVIDE TWO COPIES OF EACH PRODUCT APPROVAL. ONLY | | ONE COPY WAS SUBMITTED. | | | | 2- FLAT ROOF: | | | | A) ACCORDING TO THE MIAMI-DADE WEBSITE THE NOA | | 07-1203.01 SUBMITTED WAS SUPERSEDED. NEED TO PROVIDE | | CURRENT NOA, | | | | B) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR | | NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS | | REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA | | SUBMITTED. | | | | C) DESIGN PROFESSIONAL DOING THE RAS 117 CALCULATIONS | | TO TAKE INTO CONSIDERATION THAT ACCORDING TO THE 2009 | | REVISIONS SEC. R301.2.1.4.3 THIS BUILDING IS LOCATED IN | | EXPOSURE "C". | | | | 3- A) SPECIFY HOW IS THE CLAY TILE GOING TO BE FASTENED | | TO VERIFY COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. | | R301 OF 2007 FLORIDA RESIDENTIAL CODE. | | | | B) IF USING POLYFOAM, THEN PROVIDE 2 COPIES OF THE | | POLYFOAM PRODUCT APPROVAL. SEE CLAY TILE NOA SUBMITTED | | FOR LISTED POLYFOAM TO BE USED. | | | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712 |
|