2010-09-29 15:39:30RAS 117 CALCULATIONS CHECKLIST:
  
 1- ENGINEER NEEDS TO REVISE THE DESIGN PRESSURES.
 ACCORDING TO THE 2009 REVISIONS SEC. R301.2.1.4.3 THIS
 BUILDING IS LOCATED ON EXPOSURE "C" NOT EXPOSURE "B".
 REVISE THE DESIGN PRESSURES AS REQUIRED.
  
 ***NOTE: WHEN REVISING THE FASTENER SPACING TAKE INTO
 CONSIDERATION THAT NAILS CAN'T NOT BE SPACED LESS THAN
 4" O.C.. SEE RAS 117 SEC. 8.1.
  
 2- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712.