Plan Review Notes
Plan Review Notes For Permit 10090580
Permit Number 10090580
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-10-01 10:15:197501 NORTH JOG ROAD
 PERMIT NUMBER 10090580
 "FIRE HOSE STATIONS IN WEST BAGHOUSE INCLUDING 6"
 UNDERGROUND SUPPLY"
  
  
 1. PLEASE PROVIDE AN ELEVATION DRAWING FOR THE
 STANDPIPE SYSTEM TO INCLUDE HOSE CABINETS.
  
 2. PLEASE PROVIDE A DETAIL DRAWING OF THE HOSE CABINETS
 THAT ARE PLANNED TO BE USED.
  
 3. PLEASE PROVIDE DETAILS ON PRESSURE TESTING AND
 FLUSHING REQUIREMENTS FOR THE NEW SYSTEM TO INCLUDE THE
 UNDERGROUND FIRE MAIN AND THE FIRE DEPARTMENT
 CONNECTION.
  
 4. PLEASE PROVIDE DETAILS ON THE HOSE AND NOZZLES
 PLANNED FOR USE. WHO AND WHY DETERMINED THAT THE LENGTH
 OF HOSE BE 75 FEET. IS THE HOSE RED-LINE, COTTON
 JACKETED, OR OTHER TYPES OF FIRE HOSE.
  
 5. WHY IS THE BUILDING NOT FIRE SPRINKLER PROTECTED?
  
 6. THE FIRE DEPARTMENT CONNECTION IS TO BE EQUIPPED
 WITH KNOX LOCKING CAPS. THEY CAN BE ORDERED AT
 WWW.KNOXBOX.COM.
  
 7. PLEASE INDICATE PRESSURE, GALLONS PER MINUTE (GPM)
 AND DURATION OF WATER THAT CAN BE EXPECTED FROM THE
 STANDPIPE SYSTEM.
  
 8. PLEASE DISPLAY A RISER ELEVATION.
  
 9. PLEASE INDICATE METHODS OF PIPE RESTRAINTS FOR THE
 SYSTEM.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  
  
  