2010-10-18 11:53:34****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PROVIDE A COPY OF THE CONTRACT FOR THIS JOB.
  
 2. REVISE PLAN TO SPECIFY LETTER SIZES, FBC1609.
 ENGINEER HAS SPECIFIED MINIMUM THREE 1 1/2" TAPCONS PER
 LETTER, WITH NO LETTER SIZE. THIS PROPOSED INSTALLATION
 IS FOR LETTERS WHICH APPEAR TO BE APPROXIMATELY 3'6" X
 4' EACH, LOCATED ON A HIGH RISE. WHO DETERMINES WHEN
 MORE FASTENERS ARE REQUIRED? ARE THE THREE TAPCONS
 ADEQUATE REGARDLESS OF LETTER SIZE? "MASTER"
 ENGINEERING SHOULD INCLUDE A LIMITATION SUCH AS MAXIMUM
 LETTER SIZE OR MAX DISTANCE BETWEEN FASTENERS.
  
 CALCUATIONS TO SHOW THAT FASTENING SPECIFIED IS
 ADEQUATE MAY BE REQUIRED.
  
  