Plan Review Notes For Permit 10090573 |
Permit Number |
10090573 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-09-27 12:34:05 | 1 HARVARD CIRCLE | | PERMIT NUMBER 10090573 | | "INTERIOR ADDITION OF CONCRETE-FILLED METAL PAN | | STAIRWAY" | | | | | | 1. A FIRE SPRINKLER HEAD IS REQUIRED AT THE TOP OF THE | | STAIRWAY. ALL VERTICAL SHAFTS ARE TO BE PROTECTED BY | | SPRINKLERS WHEN PRESENT. | | | | 2. TACTILE SIGNAGE REQUIRED AT EXIT DOOR OPENING. | | | | 3. SMOKE DETECTORS ARE SHOWN WITHIN THE STAIRWELL. | | SMOKE DETECTORS ARE USUALLY NOT REQUIRED IN STAIRWELLS. | | THEY ARE NOT REQUIRED AND SHOULD BE REMOVED FROM THE | | PLANS. | | | | 4. THE RUBBER TREAD AND RISER SHALL CONTAIN SLIP | | RESISTANT PROPERTIES TO AVOID SLIP AND FALL ACCIDENTS. | | | | 5. THE PRESCRIPTIVE STRENGTH REQUIREMENTS FOR HANDRAILS | | AND GUARDRAILS SHALL MEET ALL APPLICABLE BUILDING AND | | FIRE CODE REQUIREMENTS. | | | | | | APPROVED PROVISO | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION | | | | | | |
|