Plan Review Notes
Plan Review Notes For Permit 10090470
Permit Number 10090470
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-09-28 12:29:32222 LAKEVIEW AVENUE, SUITE #1510
 PERMIT #10090470
 MASTER #10070806
  
 1) WHERE SYSTEM PRESSURES EXCEED 100 PSI, THE
 CUMULATIVE HORIZONTAL LENGTH OF AN UNSUPPORTED ARMOVER
 TO A SPRINKLER SHALL NOT EXCEED 12-INCHES PER SECTION
 9.2.3.5.2.1 OF NFPA 13 (2002 ED.).
  
 2) WHERE SYSTEM PRESSURES EXCEED 100 PSI, THE HANGER
 CLOSEST TO THE SPRINKLER SHALL BE OF A TYPE THAT
 PREVENTS UPWARD MOVEMENT OF THE PIPING PER SECTION
 9.2.3.5.2.2 OF NFPA 13 (2002 ED.).
  
 3) PROVIDE HYDRAULIC CALCULATIONS TO SUPPORT THE SIX
 SPRINKLERS (CONFERENCE ROOM AND HALLWAY) THAT ARE BEING
 SUPPLIED BY THE EXISTING 1-INCH OUTLETS ON THE 1-INCH
 BRANCH LINES.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6730