Plan Review Notes For Permit 10090470 |
Permit Number |
10090470 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-09-28 12:29:32 | 222 LAKEVIEW AVENUE, SUITE #1510 | | PERMIT #10090470 | | MASTER #10070806 | | | | 1) WHERE SYSTEM PRESSURES EXCEED 100 PSI, THE | | CUMULATIVE HORIZONTAL LENGTH OF AN UNSUPPORTED ARMOVER | | TO A SPRINKLER SHALL NOT EXCEED 12-INCHES PER SECTION | | 9.2.3.5.2.1 OF NFPA 13 (2002 ED.). | | | | 2) WHERE SYSTEM PRESSURES EXCEED 100 PSI, THE HANGER | | CLOSEST TO THE SPRINKLER SHALL BE OF A TYPE THAT | | PREVENTS UPWARD MOVEMENT OF THE PIPING PER SECTION | | 9.2.3.5.2.2 OF NFPA 13 (2002 ED.). | | | | 3) PROVIDE HYDRAULIC CALCULATIONS TO SUPPORT THE SIX | | SPRINKLERS (CONFERENCE ROOM AND HALLWAY) THAT ARE BEING | | SUPPLIED BY THE EXISTING 1-INCH OUTLETS ON THE 1-INCH | | BRANCH LINES. | | | | WESLEY JOLIN | | WEST PALM BEACH FIRE RESCUE | | FIRE & LIFE SAFETY PLAN REVIEW | | (561) 805-6730 |
|