Plan Review Notes
Plan Review Notes For Permit 10090450
Permit Number 10090450
Review Stop B
Sequence Number 1
Notes
Date Text
2010-10-22 11:10:28****CORRECTIONS****
 PERMIT APPLICATIONS 10090450, 10090451, 10090452,
 10090453, 10090454, 10090455, 10090456, 10090458
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. AN ENGINEERING EVALUATION AND SPECIFICATION FOR
 REPAIR REQUIRED, FS471. SEE ALSO CITY OF WEST PALM
 BEACH AMENDMENTS, FBC105.3. THE SCOPE OF STRUCTURAL
 REPAIRS PROPOSED DOES NOT FALL UNDER ANY EXCEPTION TO
 ENGINEERING.
  
 2. THE LETTER PROVIDED REQUESTS THAT A PERMIT BE ISSUED
 FOR "EMERGENY REPAIRS IN THE FACE OF THE HURRICANES NOW
 PRESENT." PLEASE BE ADVISED THAT A SHORING PERMIT CAN
 BE ISSUED UPON REQUEST IF AN EMERGENCY CONDITION
 EXISTS. HOWEVER, STRUCTURAL REPAIRS WOULD REQUIRE
 PLANS.
  
 3. PROVIDE A SITE PLAN WHICH SHOWS LOCATION OF PROPOSED
 REPAIRS. THE SITE PLAN FOR EACH PERMIT SHOULD SHOW THE
 BUILDING IN RELATION TO THE SITE AS WELL AS SPECIFIC
 LOCATION OF REPAIRS. APPLICATIONS WERE SUBMITTED WITH A
 SPECIFIC UNIT NUMBER AS ADDRESS. ARE REPAIRS FOR THIS
 UNIT ONLY OR TO THE COMMON AREA (EXTERIOR BUILDING
 STRUCTURE)? IF REPAIRS ARE TO THE ENTIRE BUILDING,
 PLEASE REVISE PERMIT APPLICATION. THE LETTER PROVIDED
 REFERS TO 13 BUILDINGS AND A CLUBHOUSE AND REPAIRS
 REQUIRED TO "THE BUILDINGS" BUT THE PERMIT APPLICATIONS
 APPEAR TO BE FOR BUILDING A.
  
 4. THE LETTER PROVIDED REQUESTED PERMIT NUMBERS FOR
 BALCONY REPAIR WORK DONE IN THE PAST. ONE EXAMPLE
 PERMIT NUMBER IS 08120380. I DID NOT VERIFY WHETHER OR
 NOT THIS IS THE ONLY PERMIT FOR BALCONY REPAIRS. AS
 THIS IS A LARGE COMMERCIAL PROPERTY WITH NUMEROUS
 PERMITS, I AM UNABLE TO ACCOMODATE YOUR REQUEST. YOU
 CAN OBTAIN THIS INFORMATION AT OUR WEBSITE, HTTP://ONES
 TOPSHOP.WPBGOV.COM/EGOVPLUS/PERMIT/PERM_STATUS.ASPX.
 WHEN SEARCHING BY ADDRESS, ENTER ONLY "STREET NUMBER"
 (2800) AND "STREET NAME" (GEORGIA) AND LEAVE OTHER
 FIELDS BLANK. ALTERNATELY YOU CAN SUBMIT A PUBLIC
 RECORDS REQUEST.
  
 5. PLEASE RESOLVE OTHER EXPIRED PERMITS FOR THIS
 ADDRESS AT THIS TIME.
  
 6. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR
 EXTERIOR DOORS, FAC9B72, FBC1609.
  
 7. PROVIDE A PLAN WHICH SHOWS PROPOSED DOOR REPLACEMENT
 LOCATION.
  
 8. PROPOSED DESIGN PRESSURE REQUIREMENTS FOR EXTERIOR
 DOORS REQUIRED, FBC1603.1.4.
  
 9. AFTER SCOPE OF WORK HAS BEEN DETERMINED, PROVIDE A
 COPY OF THE CONTRACT FOR THIS JOB.
  
 10. ADVISORY ONLY, NOTICE OF COMMENCEMENT WILL BE
 REQUIRED PRIOR TO FIRST INSPECTION, FS713.
  
  