Plan Review Notes For Permit 10090390 |
Permit Number |
10090390 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-10-07 15:56:16 | DENIED BY PLUMBING | | | | 1) FBC 4101.6 .3 LIMITS THE WATER VELOCITY FOR SUCTION | | PIPING TO 8 FEET PER SECOND AND ANSI/APSP-7 4.4 LIMITS | | THE WATER VELOCITY IN FIELD FABRICATED BRANCH SUCTION | | PIPING TO 6 FEET PER SECOND. THE TWO MAIN DRAINS FOR | | THE WATER FALL HAVE A PUMP WITH A MAXIMUM FLOW RATE OF | | 100 GPM. BASED ON THIS FLOW RATE WITHOUT ANY TDH | | REDUCTION FOR THE WATER VELOCITY, THE ALLOWABLE WATER | | VELOCITY IN THE 2-1/2" PIPE EXCEEDS 6 FEET PER SECOND | | AND EXCEEDS 8 FEET PER SECOND IN THE 2" PIPE. PLEASE | | SHOW HOW THE SYSTEM WILL COMPLY WITH THE REQUIRED | | MAXIMUM WATER VELOCITIES. YOU CAN USE ONE OF THE | | FOLLOWING OPTIONS : SUBMIT 2 COPIES OF TDH CALCULATIONS | | SHOWING THE ACTUAL FLOW RATE OF THE SYSTEM OR SPECIFY | | AN UNSTOPPABLE CHANNEL DRAIN OR SPECIFY LARGER PIPE | | SIZES. | | | | 2) THE CUT SHEET FOR A CHANNEL DRAIN WAS SUBMITTED, | | HOWEVER, THERE IS NO CHANNEL DRAIN SHOWN ON THE PLANS. | | PLEASE CLARIFY. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|