Plan Review Notes
Plan Review Notes For Permit 10090390
Permit Number 10090390
Review Stop P
Sequence Number 1
Notes
Date Text
2010-10-07 15:56:16DENIED BY PLUMBING
  
 1) FBC 4101.6 .3 LIMITS THE WATER VELOCITY FOR SUCTION
 PIPING TO 8 FEET PER SECOND AND ANSI/APSP-7 4.4 LIMITS
 THE WATER VELOCITY IN FIELD FABRICATED BRANCH SUCTION
 PIPING TO 6 FEET PER SECOND. THE TWO MAIN DRAINS FOR
 THE WATER FALL HAVE A PUMP WITH A MAXIMUM FLOW RATE OF
 100 GPM. BASED ON THIS FLOW RATE WITHOUT ANY TDH
 REDUCTION FOR THE WATER VELOCITY, THE ALLOWABLE WATER
 VELOCITY IN THE 2-1/2" PIPE EXCEEDS 6 FEET PER SECOND
 AND EXCEEDS 8 FEET PER SECOND IN THE 2" PIPE. PLEASE
 SHOW HOW THE SYSTEM WILL COMPLY WITH THE REQUIRED
 MAXIMUM WATER VELOCITIES. YOU CAN USE ONE OF THE
 FOLLOWING OPTIONS : SUBMIT 2 COPIES OF TDH CALCULATIONS
 SHOWING THE ACTUAL FLOW RATE OF THE SYSTEM OR SPECIFY
 AN UNSTOPPABLE CHANNEL DRAIN OR SPECIFY LARGER PIPE
 SIZES.
  
 2) THE CUT SHEET FOR A CHANNEL DRAIN WAS SUBMITTED,
 HOWEVER, THERE IS NO CHANNEL DRAIN SHOWN ON THE PLANS.
 PLEASE CLARIFY.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]