Plan Review Notes
Plan Review Notes For Permit 10090387
Permit Number 10090387
Review Stop B
Sequence Number 2
Notes
Date Text
2010-09-29 15:50:43BUILDING REVIEW SECOND CHECKLIST:
  
 1- RAS 117 CALCULATIONS SUBMITTED:
  
 A) ENGINEER NEEDS TO REVISE THE DESIGN PRESSURES.
 ACCORDING TO THE 2009 REVISIONS SEC. R301.2.1.4.3 THIS
 BUILDING IS LOCATED ON EXPOSURE "C" NOT EXPOSURE "B".
 REVISE THE DESIGN PRESSURES AS REQUIRED.
  
 B) ***NOTE: WHEN REVISING THE FASTENER SPACING TAKE
 INTO CONSIDERATION THAT NAILS CAN'T NOT BE SPACED LESS
 THAN 4" O.C.. SEE RAS 117 SEC. 8.1.
  
 2- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712.