Plan Review Notes For Permit 10090387 |
Permit Number |
10090387 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2010-09-29 15:50:43 | BUILDING REVIEW SECOND CHECKLIST: | | | | 1- RAS 117 CALCULATIONS SUBMITTED: | | | | A) ENGINEER NEEDS TO REVISE THE DESIGN PRESSURES. | | ACCORDING TO THE 2009 REVISIONS SEC. R301.2.1.4.3 THIS | | BUILDING IS LOCATED ON EXPOSURE "C" NOT EXPOSURE "B". | | REVISE THE DESIGN PRESSURES AS REQUIRED. | | | | B) ***NOTE: WHEN REVISING THE FASTENER SPACING TAKE | | INTO CONSIDERATION THAT NAILS CAN'T NOT BE SPACED LESS | | THAN 4" O.C.. SEE RAS 117 SEC. 8.1. | | | | 2- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 | | FLORIDA STATUTE. | | | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561)805-6712. |
|