Plan Review Notes
Plan Review Notes For Permit 10090281
Permit Number 10090281
Review Stop B
Sequence Number 2
Notes
Date Text
2010-11-19 17:10:48RESIDENTIAL (R3) ADDITION, BUILDING REVIEW SECOND
 CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- NEED RECORDED NOTICE OF COMMENCEMENT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 2- ENERGY CALCULATIONS SUBMITTED:
 A) R30 BUTT INSULATION DOESN'T FIT ON 2X8 ROOF RAFTERS.
 R30 BUTT INSULATION IS ABOUT 9 1/2" THICK. CLARIFY HOW
 IS THE ROOF CROSS VENTILATION REQUIRED BY SEC. R806
 GOING TO BE ACHIEVED. ALSO, THE INSULATION VALUE WILL
 NEED TO BE REDUCED IF THE BUTT INSULATION IS COMPRESSED
 TO FIT WITHIN THE ROOF RAFTERS.
  
 B) PERSON WHO PREPARED THE ENERGY CALCULATIONS NEED TO
 SIGN AND DATE AT THE BOTTOM OF THE ENERGY CALCULATIONS
 SUBMITTED.
  
 3- FLAT ROOF PRODUCT APPROVAL SUBMITTED:
 A) CLEARLY MARK ON NOA SUBMITTED SPECIFIC APPROVED
 ASSEMBLY TO BE INSTALLED. (REPEAT COMMENT. NOT
 ADDRESSED).
  
 B) ENGINEER TO PROVIDE THE RAS 117 CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 SUBMITTED.
  
 ***INFORMATION SUBMITTED DOESN'T SHOW THE RAS 117
 CALCULATIONS. ENGINEER TO IDENTIFY WHICH APPROVED
 ASSEMBLY HE'S USING. BASE SHEET FASTENING
 SPECIFICATIONS PROVIDED BY THE ENGINEER ARE NO CLEAR.
 ENGINEER TO PROVIDE SKETCH SHOWING PROPOSED NAILING.
 ENGINEER TO IDENTIFY EACH ROOF ZONE.
  
 ***NOTE: APPROVED ASSEMBLIES THAT ARE LIMITED BY
 GENERAL LIMITATION #9 CAN'T BE USED IN THIS AREA.
  
 4- STORM SHUTTERS:
 A) PROVIDE COMPLETE INSTALLATION SCHEDULE. (REPEAT
 COMMENT. NOT ADDRESSED).
  
 B) CLEARLY MARK ON SHUTTERS DRAWINGS SPECIFIC MOUNTING
 CONDITIONS (EX: WALL MOUNTED, BUILD OUT, ETC) AND
 SPECIFIC ANCHOR TYPE AND SPACING TO BE USED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC. R301.
 (REPEAT COMMENT. NOT ADDRESSED).
  
 5- SHEET A-2.0:
 A) ROOF ZONE #3 REQUIRES MIN. 8D RING SHANK NAILS AT 4"
 O.C. AS REQUIRED BY SEC. R803.2.3.1 OF 2007 FLORIDA
 RESIDENTIAL CODE. REVISE ALL ROOF SHEATHING NOTES AND
 DETAILS AS REQUIRED TO REFLECT THIS REQUIREMENTS.
  
 B) REVISE COMPONENT AND CLADDING PRESSURE ZONES TABLE
 TO REFLECT THE ROOF SHEATHING NAIL TYPE AND SPACING AS
 REQUIRED ON ITEM 5A ABOVE.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  