2010-09-13 11:43:092007 FBC W/2009 REVISIONS
 DENIED BY BUILDING
  
 1) THE PRODUCT APPROVAL THAT WAS SUBMITTED NOA NO.
 07-0730.03 HAS BEEN REVISED BY NOA NO. 09-0820.11.
 SUBMIT TWO COPIES OF THE CURRENT NOA.
  
 2) THE SUBMITTAL SPECIFIES THE SYSTEM ON PAGE 16 OF THE
 NOA, BUT DOES NOT SPECIFY WHICH FASTENING OPTION WILL
 BE USED. INDICATE THE FASTENING OPTION THAT WILL BE
 USED.
  
 3) THE DESIGN PRESSURE FOR FASTENING OPTION #1 IS -52.5
 PSF. THIS IS NOT ADEQUATE FOR THE PERIMETER AND CORNER
 AREAS OF THE FLAT ROOF WHICH HAS HIGHER UPLIFT PRESSURE
 REQUIREMENTS. THE NOA ALLOWS INCREASED FASTENER
 DENSITIES IN THESE AREAS CALCULATED IN ACCORDANCE WITH
 RAS 117 IN ORDER TO ENHANCE THE DESIGN PRESSURE. SEE
 LIMITATION NUMBER 7 ON PAGE 18. SUBMIT TWO COPIES OF
 THE ENHANCED FASTENING CALCULATIONS.
  