Plan Review Notes For Permit 10090231 |
Permit Number |
10090231 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-09-13 11:43:09 | 2007 FBC W/2009 REVISIONS | | DENIED BY BUILDING | | | | 1) THE PRODUCT APPROVAL THAT WAS SUBMITTED NOA NO. | | 07-0730.03 HAS BEEN REVISED BY NOA NO. 09-0820.11. | | SUBMIT TWO COPIES OF THE CURRENT NOA. | | | | 2) THE SUBMITTAL SPECIFIES THE SYSTEM ON PAGE 16 OF THE | | NOA, BUT DOES NOT SPECIFY WHICH FASTENING OPTION WILL | | BE USED. INDICATE THE FASTENING OPTION THAT WILL BE | | USED. | | | | 3) THE DESIGN PRESSURE FOR FASTENING OPTION #1 IS -52.5 | | PSF. THIS IS NOT ADEQUATE FOR THE PERIMETER AND CORNER | | AREAS OF THE FLAT ROOF WHICH HAS HIGHER UPLIFT PRESSURE | | REQUIREMENTS. THE NOA ALLOWS INCREASED FASTENER | | DENSITIES IN THESE AREAS CALCULATED IN ACCORDANCE WITH | | RAS 117 IN ORDER TO ENHANCE THE DESIGN PRESSURE. SEE | | LIMITATION NUMBER 7 ON PAGE 18. SUBMIT TWO COPIES OF | | THE ENHANCED FASTENING CALCULATIONS. | | | | ROBERT MCDOUGAL | | BLDG. PLAN REVIEW | | (561)805-6714 | | [email protected] |
|