Plan Review Notes
Plan Review Notes For Permit 10090192
Permit Number 10090192
Review Stop B
Sequence Number 1
Notes
Date Text
2010-09-16 15:20:04PURE VIDA
 700 SOUTH ROSEMARY AVENUE
 PERMIT NUMBER 10090192
  
  
 1. ON SHEET A-1.0 IN THE CODE /PROJECT DESIGN BOX IT
 REFERENCES BB KINGS, 550 SOUTH ROSEMARY AVENUE BUT THE
 PLANS ILLUSTRATE A TENANT SPACE AT 700 SOUTH ROSEMARY
 AVENUE.
  
 2. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM SYSTEM INSTALLATIONS AND
 REMODELS.
  
 3. SINCE THE OCCUPANT LOAD IS EXPECTED TO BE ABOVE 250
 PERSONS CROWD MANAGEMENT TRAINING IS REQUIRED. PLEASE
 HAVE SELECTED PERSONNEL GO TO WWW.MARYLAND STATE FIRE
 MARSHAL'S OFFICE AND CLICK THE CROWD MANAGEMENT ICON.
 STAFF MEMBERS ARE TO WATCH THE VIDEO AND TAKE THE TEST.
 COPIES OF CERTIFICATES ARE TO BE SUBMITTED TO THE FIRE
 MARSHAL'S OFFICE PRIOR TO OPENING. OVERCROWDING IS NOT
 PERMITTED WITHIN THE ESTABLISHMENT. THE FINAL OCCUPANT
 LOAD WILL BE DETERMINED BY THIS OFFICE AND WILL BE
 REQUIRED TO BE POSTED. STAFF MEMBERS ARE TO CLICK IN
 AND OUTS TO PREVENT OVERCROWDING.
  
 4. ALL RATED FIRE DOORS ARE TO BE EQUIPPED WITH FIRE
 RATED PANIC HARDWARE. OTHER EXIT DOORS ARE TO BE
 EQUIPPED WITH PANIC HARDWARE.
  
 5. IT APPEARS THAT THE LOUNGE/SEATING AREA 105 IS TOO
 CROWDED. PLEASE REVIEW AREA TO DETERMINE ADEQUATE EXIT
 ACCESS.
  
 6. ALL EXISTING FIRE WALLS IF DAMAGED ARE TO BE
 REPAIRED TO PREVIOUS CONDITION. ALL PIPE PENETRATIONS
 ARE TO BE SEALED IN AN APPROVED MANNER WITH APPROVED
 MATERIALS FOR THAT PURPOSE.
  
 7. THE FIRE ALARM SYSTEM IS REQUIRED TO PROVIDE VOICE
 EVACUATION INSTRUCTIONS TO THE OCCUPANTS UPON
 ACTIVATION OF THE FIRE ALARM SYSTEM. PLEASE INDICATE
 WHAT THE VOICE EVACUATION PROMPTS WILL INDICATE TO
 VISITORS TO DO IN THE EVENT OF AN EMERGENCY.
  
 8. ALL COOLERS AND FREEZERS ARE TO BE FIRE SPRINKLER
 PROTECTED.
  
 9. PLEASE DEMONSTRATE COMPLIANCE WITH FIRE RETARDANT
 CRITERIA FOR THE TIKI COVERING MATERIAL SHOWN ON SHEET
 A-5.0.
  
 10. THE INSTALLATION OF ANY SOFFIT MATERIAL SHALL NOT
 INTERFERE WITH THE OPERATION OF ANY FIRE SPRINKLER
 HEADS.
  
  
 DENIED
  
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION