Plan Review Notes For Permit 10090185 |
Permit Number |
10090185 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-09-29 08:47:42 | BRANCH CIRCUITS SHALL COMPLY WITH 210.12 B | | | | ALL RECEPTACLE OUTLETS SHALL BE TAMPER RESISTANT. | | 406.11 | | | | MEANS SHALL BE PROVIDED FOR BONDING/GROUNDING OTHER | | SYSTEMS AT THE SERVICE 250.94 | | | | OUTDOOR OUTLETS SHALL BE WEATHER RESISTANT. 406.8 | | | | DESCRIPTION OF BRACH CIRCUITS NEED TO BE MORE SPECIFIC, | | 408.4 | | | | OUTLET SPACING AS SHOWN ON DRAWINGS DOES NOT MEET THE | | SPACING REQUIREMENTS OF 210.52 A 1,2 | | KITCHEN COUNTER, HALLWAY,BEDROOMS ALL HAVE OUTLET | | SPACING VIOLATIONS. | | | | NO COMPRESSOR CIRCUIT SHOWN ON PANEL SCHEDULE OR | | DRAWING (LOCATION) | | | | EMERGENCY PANEL SCHEDULE NOT SHOWN. | | | | NEED SIZE OF PANEL SIZE OF WIRE, LISTING ON GENERATOR | | RECEPTACLE (EMERGENCY SYSTEM) | | | | OULETS ON OUTSIDE WALLS THAT ARE FACING OUTDOORS SHALL | | BE CONSIDERED A WET/DAMP LOCATION SEE 334.12 B 4 | | | | |
|