2010-09-07 09:22:19 | BUILDING PLAN REVIEW | | PERMIT: 10060144 | | ADD: 338 MURRAY RD | | CONT: O/B BROOKS, JAMES | | TEL: (561)685-4340 | | | | FL BLD CODE= 2007 FLORIDA BUILDING CODE | | W/ 2009 FBC SUPPLEMENTS | | * WEST PALM BEACH AMENDMENTS | | | | | | BUILDING PROVISOS: | | | | 1) FLAT ROOF: | | FL1654-R4 | | POLYGLASS- MODIFIED BITUMEN ROOF SYSTEMS | | APPENDIX1, PAGE 10 OF 33 | | W-26 SYSTEM -60.0 PSF | | ZONES 2 & 3 REQUIRE ENHANCED FASTENING | | LIMITATION 5.6 DOES ALLOW ENHANCED FASTENING IN ZONES | | 2&3 BY A QUALIFIED DESIGN PROFESSIONAL. | | TO BE PROVIDED AT TIME OF ROOFING PERMIT APPLICATION. | | | | METAL ROOF: OK!!! | | FL 11698 | | ENGLERT INC. | | DESIGN UPLIFT OF -124 PSF. C-BUCK ENGINEERING PRODUCT | | APPROVAL. | | |
|