2011-05-27 13:51:31 | PLUMBING PLAN REVIEW |
| PERMIT: 10090080MASTER |
| PLUMB: 10090078 |
| ADD: 926 SUNSET RD |
| TEL: (561)718-4600 |
| FL BLD CODE= 2007 FLORIDA BUILDING CODE- W/ 2009 FBC |
| SUPPLEMENTS |
| MAY 19/ 2011 |
| |
| PLUMBING PLAN REVIEW |
| PLUMBING PROVISO: |
| |
| |
| |
| |
| 1) A REVISION WILL BE REQUIRED FOR THE PLUMBING |
| DRAINAGE FLOOR PLAN & SANITARY ISOMETRIC. THE CURRENT |
| LAYOUT INDICATES THE KITCHEN AND WASHING MACHINE DRAINS |
| TYING INTO A WET VENT (BATHROOM GROUP) A PLUMBING CODE |
| VIOLATION PER (FBC-P909.1). THE PREVIOUS PLAN REVIEW |
| REQUESTED A VIDEO OF THE SANITARY AND ISOMETRIC OF WHAT |
| WAS INSTALLED WITHOUT PERMIT. THE ISOMETRIC WAS NOT |
| DELIVERED BUT THE VIDEO WAS PRESENTED AND IT IS EVIDENT |
| IN THE VIDEO THE PIPES ARE BACK PITCHED RETAINING WATER |
| IN THE PIPES CREATING A SECOND CODE ISSUE (FBC-P |
| 704.1/TABLE 704.1). IT APPEARS THAT THE INSTALLATION |
| MAY HAVE BEEN INSTALLED BY AN O/B, AND WE WOULD SUGGEST |
| YOU CONTACT A PLUMBING CONTRACTOR TO CORRECT THE CODE |
| VIOLATIONS WITH NEW SANITARY OR PORTION THERE OF AND |
| REVISION. WE WOULD BE GLAD TO MEET WITH WHOEVER YOU |
| WOULD LIKE BEFORE WORK BEGINS. NOTE THIS REVISION WOULD |
| NEED TO BE SEALED BY THE DESIGNER OF RECORD. |
| |
| |
| |
| JIM WITMER C. B. O. |