Plan Review Notes For Permit 10090070 |
Permit Number |
10090070 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2011-01-12 12:19:27 | FBC PLUMBING 2007 REVIEW #2 | | DENIED: | | | | 1. THE MOP SINK WILL BE REQUIRED TO BE CONNECTED TO THE | | GREASE TRAP. FBC PLUMBING 2007 1003.3.1 GREASE | | INTERCEPTORS AND AUTOMATIC GREASE REMOVAL DEVICES | | REQUIRED. A GREASE INTERCEPTOR OR AUTOMATIC GREASE | | REMOVAL DEVICE SHALL BE REQUIRED TO RECEIVE THE | | DRAINAGE FROM FIXTURES AND EQUIPMENT WITH GREASE-LADEN | | WASTE | | | | 2. THE EQUIPMENT SCHEDULE ON SHEET A-1 CALLS FOR A 50 | | GALLON GREASE TRAP WHICH WOULD BE CORRECT FOR A THREE | | COMPARTMENT SINK AND MOPSINK. THE GREASE TRAP ON P-1 | | ZURN GT 2700-25 IS 25 GALLONS PER MINUTE.(PDI | | CALCULATES A TYPICAL THREE COMPARTMENT SINK AT 33.7 GPM | | FLOW). | | | | 3. A WATER PIPE DRAWING IS REQUIRED FBC 106.3.5.1.3 | | | | 4. A DBPR HEALTH DEPT. PLAN OK WILL BE REQUIRED BEFORE | | PERMIT ISSUANCE. HTTP://WWW.MYFLORIDALICENSE.COM/DBPR/H | | R/FORMS/PLANREVIEWFORMS.HTML | | | | 5. THE PERMIT APPLICATION INDICATES THE SCOPE OF WORK | | FOR THIS PERMIT IS TO BUILD A NEW ADA SERVICE COUNTER. | | A NEW COMMERCIAL KITCHEN IS THE SCOPE OF WORK TO BE | | DESCRIBED UNDER THIS PERMIT, ALSO THE VALUE OF THIS | | PROJECT LOOKS TO BE TOO LOW (LISTED AS $1,000 ). | | | | REVIEW BY LARRY WAGNER | | CHIEF PLUMBING INSPECTOR | | (561) 805-6692 | | FAX (561) 653-2692 | | E-MAIL [email protected] | | |
|