Plan Review Notes For Permit 10090070 |
Permit Number |
10090070 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2011-01-12 14:39:05 | ELECTRIC PERMIT REQUIRED. | | REVISE SCOPE OF WORK AND VALUE TO REFLECT NEW ELECTRIC | | WORK | | UPDATE PERMIT FEE TO REFLECT VALUE OF WORK | | PROVIDE SIGN CIRCUIT. NEC 600.5 | | PROVIDE A BONDING BAR AT THE SERVICE. NEC 250.94 | | | | | | ROBERT LECKY, ELECTRIC PLANS EXAMINER, 561-805-6718 |
|