Notes
Date Text
2010-09-28 12:00:06MECHANICAL PLANS DENIED
 1) SEPARATE PERMIT AND PLANS REQUIRED FOR GREASE HOOD .
 2) PLEASE REFER TO SECTION 506.3.12.3 TERMINATION
 LOCATION 2007 FBC. (M)
 3) PLEASE PROVIDE A DETAIL FOR THE EXHAUST AND SUPPLY
 FAN CURBS TIE DOWN TO THE ROOF ,FROM THE ENGINEER.
 PLAN REVIEW BY HAROLD MOSER 561-805-6732