Plan Review Notes For Permit 10090070 |
Permit Number |
10090070 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-09-27 10:42:09 | 4310 BROADWAY AVENUE | | PERMIT NUMBER 10090070 | | "BUILD-NEW ADA SERVICE COUNTER" | | | | | | 1. ON SHEET A-1 AN EXHAUST HOOD IS SHOWN BUT ON PAGE | | M-1 A NEW GREASE HOOD IS SHOWN. SEPARATE PLANS AND | | PERMITS REQUIRED FOR THE INSTALLATION OF A HOOD, DUCT, | | AND FIRE SUPPRESSION SYSTEM. THE HOOD EXTINGUISHING | | SYSTEM SHALL MEET THE REQUIREMENTS OF THE UL 300 | | STANDARD. | | | | 2. ON SHEET M-1 A REVISION FOR A RAISED PARAPET IS | | SHOWN. THIS WORK DOES NOT CORRESPOND TO INFORMATION | | LISTED ON THE PERMIT APPLICATION. | | | | | | DENIED | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION | | | | | | | | |
|