2010-09-27 10:42:094310 BROADWAY AVENUE
 PERMIT NUMBER 10090070
 "BUILD-NEW ADA SERVICE COUNTER"
  
  
 1. ON SHEET A-1 AN EXHAUST HOOD IS SHOWN BUT ON PAGE
 M-1 A NEW GREASE HOOD IS SHOWN. SEPARATE PLANS AND
 PERMITS REQUIRED FOR THE INSTALLATION OF A HOOD, DUCT,
 AND FIRE SUPPRESSION SYSTEM. THE HOOD EXTINGUISHING
 SYSTEM SHALL MEET THE REQUIREMENTS OF THE UL 300
 STANDARD.
  
 2. ON SHEET M-1 A REVISION FOR A RAISED PARAPET IS
 SHOWN. THIS WORK DOES NOT CORRESPOND TO INFORMATION
 LISTED ON THE PERMIT APPLICATION.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  
  
  
  