Plan Review Notes
Plan Review Notes For Permit 10080805
Permit Number 10080805
Review Stop B
Sequence Number 1
Notes
Date Text
2010-09-08 10:44:23****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. SEE OPENING 2, HORIZONTAL INSTALLATION REQUIRES USE
 OF MASONRY SUBSTRATE CHART OR PROVIDE EVIDENCE THAT
 BOTH SIDES ARE FORMED AND POURED CONCRETE. ANCHOR
 SPACING PROPOSED DOES NOT COMPLY WITH REQUIREMENTS OF
 THE PRODUCT APPROVAL.
  
 2. SEE OPENING 3, 16" SPACING DOES NOT COMPLY WITH THE
 REQUIRMENTS OF THE PRODUCT APPROVAL. NOTE THAT TOP AND
 BOTOTM HAVE SAME CONNECTION TYPE, SAME SUBSTRATE, ETC.
 BUT DIFFERENT ANCHOR SPACING.
  
 3. THE INFORMATION HIGHLIGHTED ON THE PRODUCT APPROVAL
 SHOULD CORRELATE WITH THE INSTALLATION SCHEDULE.
 TAPCONS SPECIFIED ON THE INSTALLATION SCHEDULE, ELCO
 PANELMATE HIGHLIGHTED. PLEASE CORRELATE.
  
  