Plan Review Notes For Permit 10080805 |
Permit Number |
10080805 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-09-08 10:44:23 | ****CORRECTIONS**** | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | FBC FLORIDA BUILDING CODE 2007 | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | 1. SEE OPENING 2, HORIZONTAL INSTALLATION REQUIRES USE | | OF MASONRY SUBSTRATE CHART OR PROVIDE EVIDENCE THAT | | BOTH SIDES ARE FORMED AND POURED CONCRETE. ANCHOR | | SPACING PROPOSED DOES NOT COMPLY WITH REQUIREMENTS OF | | THE PRODUCT APPROVAL. | | | | 2. SEE OPENING 3, 16" SPACING DOES NOT COMPLY WITH THE | | REQUIRMENTS OF THE PRODUCT APPROVAL. NOTE THAT TOP AND | | BOTOTM HAVE SAME CONNECTION TYPE, SAME SUBSTRATE, ETC. | | BUT DIFFERENT ANCHOR SPACING. | | | | 3. THE INFORMATION HIGHLIGHTED ON THE PRODUCT APPROVAL | | SHOULD CORRELATE WITH THE INSTALLATION SCHEDULE. | | TAPCONS SPECIFIED ON THE INSTALLATION SCHEDULE, ELCO | | PANELMATE HIGHLIGHTED. PLEASE CORRELATE. | | | | |
|