Plan Review Notes
Plan Review Notes For Permit 10080752
Permit Number 10080752
Review Stop B
Sequence Number 1
Notes
Date Text
2010-09-07 18:00:49BUILDING PLAN REVIEW
 PERMIT: 10080752
 ADD: 5200 N FLAGLER DR SUITE# 1601
 CONT: A & A DEVELOPMENT
 TEL: (561)719-0895
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING APPROVED WITH EXCEPTION!
 THIS PLAN HAS BEEN APPROVED PROVISIONALLY. FAILURE TO
 CORRECT THE LISTED DEFICIENCIES IN THIS PLAN PRIOR TO
 INSPECTION WILL RESULT IN FAILED INSPECTION(S) AND THE
 ASSESSMENT OF RE-INSPECTION FEE(S). REVISIONS REQUIRE
 ADDITIONAL REVIEWS WITH ASSOCIATED FEES.
  
 1) TYPE I AND TYPE II CONSTRUCTION: 603.1 ALLOWABLE
 MATERIALS.(1).FIRE-RETARDANT-TREATED WOOD SHALL BE
 PERMITTED .
  
 2) 1207.2 AIR-BORNE SOUND. WALLS, PARTITIONS AND
 FLOOR/CEILING ASSEMBLIES SEPARATING DWELLING UNITS FROM
 EACH OTHER OR FROM PUBLIC OR SERVICE AREAS SHALL HAVE A
 SOUND TRANSMISSION CLASS (STC) OF NOT LESS THAN 50 (45
 IF FIELD TESTED) FOR AIR-BORNE NOISE WHEN TESTED IN
 ACCORDANCE WITH ASTM E 90. PENETRATIONS OR OPENINGS IN
 CONSTRUCTION ASSEMBLIES FOR PIPING; ELECTRICAL DEVICES;
 RECESSED CABINETS; BATHTUBS; SOFFITS; OR HEATING,
 VENTILATING OR EXHAUST DUCTS SHALL BE SEALED, LINED,
 INSULATED OR OTHERWISE TREATED TO MAINTAIN THE REQUIRED
 RATINGS. THIS REQUIREMENT SHALL NOT APPLY TO DWELLING
 UNIT ENTRANCE DOORS; HOWEVER, SUCH DOORS SHALL BE TIGHT
 FITTING TO THE FRAME AND SILL.
  
 3) 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING
 ASSEMBLIES BETWEEN DWELLING UNITS OR BETWEEN A DWELLING
 UNIT AND A PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE
 SHALL HAVE AN IMPACT INSULATION CLASS (IIC) RATING OF
 NOT LESS THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN
 ACCORDANCE WITH ASTM E 492.
  