Plan Review Notes For Permit 10080745 |
Permit Number |
10080745 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-08-30 12:31:24 | PALM BEACH ATLANTIC UNIVERSITY | | 500 FERN STREET | | PERMIT NUMBER 10080745 | | | | 1. NO FIRE ALARM SIGNALING APPLIANCES LOCATED IN | | DRESSING ROOM, DESIGN ROOM, AREA OPPOSITE OF WORK | | CENTER, OR COSTUME SHOP STORAGE. | | | | 2. NO SEQUENCE OF OPERATION INFORMATION PROVIDED WITH | | DRAWINGS. | | | | 3. PLANS DO NOT INDICATE WHAT THE VOICE EVACUATION | | PORTION OF THE FIRE ALARM SYSTEM WILL STATE. | | | | 4. NO SMOKE DETECTORS, HEAT DETECTORS, OR DUCT | | DETECTORS DISPLAYED ON THE PLANS. | | | | 5. NO NOTES PROVIDED FOR THE DRAWINGS. | | | | 6. NO SMOKE DETECTOR DISPLAYED ABOVE FIRE ALARM CONTROL | | PANEL. | | | | 7. NO INFORMATION PROVIDED REGARDING COMMUNICATION | | METHODS FOR FIRE ALARM CONTROL PANEL. | | | | 8. FOUR SIGNALS ARE REQUIRED FOR THE FIRE ALARM SYSTEM | | TO TRANSMIT. THEY ARE GENERAL FIRE ALARM, SUPERVISORY, | | TROUBLE AND WATERFLOW. | | | | 9. THE FIRE ALARM SYSTEM SHALL BE EITHER UL OR FM | | APPROVED FOR MONITORING FOR CENTRAL STATION SERVICE. | | | | ON AUGUST 30, 2010, THIS WRITER MET WITH KEN WEBB TO | | DISCUSS THESE DEFICIENCIES. | | | | | | DENIED | | | | | | MIKE CARSILLO, BATTALION CHIEF | | BUREAU OF FIRE PREVENTION |
|