Plan Review Notes
Plan Review Notes For Permit 10080745
Permit Number 10080745
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-08-30 12:31:24PALM BEACH ATLANTIC UNIVERSITY
 500 FERN STREET
 PERMIT NUMBER 10080745
  
 1. NO FIRE ALARM SIGNALING APPLIANCES LOCATED IN
 DRESSING ROOM, DESIGN ROOM, AREA OPPOSITE OF WORK
 CENTER, OR COSTUME SHOP STORAGE.
  
 2. NO SEQUENCE OF OPERATION INFORMATION PROVIDED WITH
 DRAWINGS.
  
 3. PLANS DO NOT INDICATE WHAT THE VOICE EVACUATION
 PORTION OF THE FIRE ALARM SYSTEM WILL STATE.
  
 4. NO SMOKE DETECTORS, HEAT DETECTORS, OR DUCT
 DETECTORS DISPLAYED ON THE PLANS.
  
 5. NO NOTES PROVIDED FOR THE DRAWINGS.
  
 6. NO SMOKE DETECTOR DISPLAYED ABOVE FIRE ALARM CONTROL
 PANEL.
  
 7. NO INFORMATION PROVIDED REGARDING COMMUNICATION
 METHODS FOR FIRE ALARM CONTROL PANEL.
  
 8. FOUR SIGNALS ARE REQUIRED FOR THE FIRE ALARM SYSTEM
 TO TRANSMIT. THEY ARE GENERAL FIRE ALARM, SUPERVISORY,
 TROUBLE AND WATERFLOW.
  
 9. THE FIRE ALARM SYSTEM SHALL BE EITHER UL OR FM
 APPROVED FOR MONITORING FOR CENTRAL STATION SERVICE.
  
 ON AUGUST 30, 2010, THIS WRITER MET WITH KEN WEBB TO
 DISCUSS THESE DEFICIENCIES.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION