Plan Review Notes For Permit 10080641 |
Permit Number |
10080641 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2010-09-10 11:19:01 | REVIEW #: 1ST | | ACTION: DENIED | | | | FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | PLAN REVIEW COMMENTS: | | | | 1. PROVIDE SYMBOL LEGEND FOR ALL HVAC PLANS. SOME | | SYMBOLS ARE IDENTIFIED WITH ARROWS AND NOTES WHILE | | OTHERS ARE NOT. PLEASE CLARIFY PER FBC-B 106.1.1. | | | | 2. PLANS INDICATE SEVERAL SPACES ARE BEING | | RECONFIGURED. ALL RECONFIGURED SPACES INTENDED FOR | | OCCUPANCY IN ANY WORK AREA SHALL BE PROVIDED WITH | | MECHANICAL VENTILATION OR EXHAUST IN ACCORDANCE WITH | | THE FLORIDA BUILDING CODE, MECHANICAL PER FBC-EB 709.1 | | SEE FBC-M SECTION 403 FOR MECHANICAL VENTILATION | | REQUIREMENTS AND PROVIDE SPACE-BY-SPACE CALCULATIONS | | BASED ON FBC-M TABLE 403.3. ALSO, PROVIDE AIR | | QUANTITIES ON PLANS TO FACILITATE PROPER TEST AND | | BALANCE OF AIR DISTRIBUTION SYSTEM FOR NEW RATES PER | | FBC-M 403.3.4. | | | | 3. PAGE A-11 SHOWS CONFLICTING RETURN GRILLS IN CEILING | | OF THE NEW WAITING ROOM. PLEASE CLARIFY. FBC-B 106.1.1. | | | | 4. PAGE A-19: TERMINAL BOX 1-1 APPEARS TO BE ELIMINATED | | FROM REVISED HVAC PLAN WHILE THE DUCT IS STILL SHOWN | | FEEDING NEW OFFICE #2. PLEASE CLARIFY PER FBC-M 603.1. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] |
|