2010-09-10 11:19:01REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2007 CODE FAMILY W/ 2009 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 PLAN REVIEW COMMENTS:
  
 1. PROVIDE SYMBOL LEGEND FOR ALL HVAC PLANS. SOME
 SYMBOLS ARE IDENTIFIED WITH ARROWS AND NOTES WHILE
 OTHERS ARE NOT. PLEASE CLARIFY PER FBC-B 106.1.1.
  
 2. PLANS INDICATE SEVERAL SPACES ARE BEING
 RECONFIGURED. ALL RECONFIGURED SPACES INTENDED FOR
 OCCUPANCY IN ANY WORK AREA SHALL BE PROVIDED WITH
 MECHANICAL VENTILATION OR EXHAUST IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, MECHANICAL PER FBC-EB 709.1
 SEE FBC-M SECTION 403 FOR MECHANICAL VENTILATION
 REQUIREMENTS AND PROVIDE SPACE-BY-SPACE CALCULATIONS
 BASED ON FBC-M TABLE 403.3. ALSO, PROVIDE AIR
 QUANTITIES ON PLANS TO FACILITATE PROPER TEST AND
 BALANCE OF AIR DISTRIBUTION SYSTEM FOR NEW RATES PER
 FBC-M 403.3.4.
  
 3. PAGE A-11 SHOWS CONFLICTING RETURN GRILLS IN CEILING
 OF THE NEW WAITING ROOM. PLEASE CLARIFY. FBC-B 106.1.1.
  
 4. PAGE A-19: TERMINAL BOX 1-1 APPEARS TO BE ELIMINATED
 FROM REVISED HVAC PLAN WHILE THE DUCT IS STILL SHOWN
 FEEDING NEW OFFICE #2. PLEASE CLARIFY PER FBC-M 603.1.
  