Plan Review Notes
Plan Review Notes For Permit 10080639
Permit Number 10080639
Review Stop B
Sequence Number 2
Notes
Date Text
2011-02-02 15:14:43ADD: 2510 BROADWAY
 CONT: JHAMTREE
 TEL: (561)602-0009
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
 2ND REVIEW
  
 1A) COMPLIED.
  
 1B) SEMI- COMPLIED. SHEET SP-1 INDICATES AN OCCUPANT
 LOAD OF 52 OCCUPANTS, PLEASE REVIEW SECTION / TABLE
 1015.1 WHICH WILL REQUIRE (2) POINTS OF EGRESS, AND
 THEY WILL TO MEET THE REQUIREMENT FOR 1/2 THE DIAGONAL
 DISTANCE APART FBC-B 1015.2.1.
  
 1C) THE PROPOSED DOOR# (02) IS LOCATED2.5 FEET FROM
 THTE PROPERTY LINE SEE SP-1, PLEASE REVIEW FBC-B TABLE
 704.7 FOR ALLOWABLE OPENINGS, UNPROTECTED OR PROTECTED,
 0-5 FEET OPENINGS ARE NOT ALLOWED.
  
 2-6) COMPLIED.
  
 7) EVEN IF THE DESIGNEER OF RECORD PULL THE DOOR# 02
 BACK BEYOND THE 0-3' ALLOWING FOR PROTECTED OPENINGS
 THE OTHER ISSUE WILL BE WITH THE EXIT DISCHARGE MEETING
 THESE REQUIREMENTS:
  
 2007/ 2009 FBC-B 1024.3 EXIT DISCHARGE LOCATION.
 EXTERIOR BALCONIES, STAIRWAYS AND RAMPS SHALL BE
 LOCATED AT LEAST 10 FEET (3048 MM) FROM ADJACENT LOT
 LINES AND FROM OTHER BUILDINGS ON THE SAME LOT UNLESS
 THE ADJACENT BUILDING EXTERIOR WALLS AND OPENINGS ARE
 PROTECTED IN ACCORDANCE WITH SECTION 704 BASED ON FIRE
 SEPARATION DISTANCE.
  
 2007/ 2009 FBC-B 1024.4 EXIT DISCHARGE COMPONENTS. EXIT
 DISCHARGE COMPONENTS SHALL BE SUFFICIENTLY OPEN TO THE
 EXTERIOR SO AS TO MINIMIZE THE ACCUMULATION OF SMOKE
 AND TOXIC GASES.
  
 2007/ 2009 FBC-B 1024.5 EGRESS COURTS. EGRESS COURTS
 SERVING AS A PORTION OF THE EXIT DISCHARGE IN THE MEANS
 OF EGRESS SYSTEM SHALL COMPLY WITH THE REQUIREMENTS OF
 SECTION 1024.
  
 2007/ 2009 FBC-B 1024.5.1 WIDTH. THE WIDTH OF EGRESS
 COURTS SHALL BE DETERMINED AS SPECIFIED IN SECTION
 1005.1, BUT SUCH WIDTH SHALL NOT BE LESS THAN 44
 INCHES.
  
 THE CONTRACTOR SUBMITTED A PRODUCT APPROVAL FOR DOOR #
 2 QUALITY ENGINEERED PRODUCT CO. INC. FOR WIND AND
 LARGE MISSILE IMPACT BUT NO TESTING REPORT FOR THE FIRE
 RATING OF DOOR, 2007/ 2009 FBC-B TABLE 715.4.
  
 8) THE COVER SHEET INDICATES THE PREVIOUS TENANT TO BE
 A AUTO REPAIR GARAGE MAKING THIS A S-1 OCCUPANCY. A
 CHANGE IN OCCUPANCY REQUIRES IMPACT FEE REVIEW. BEFORE
 A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST
 BE PAID TO PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF
 PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE
 PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE
 CALL (561)233-5025 FOR MORE INFORMATION.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
  
  
  