2011-02-02 15:14:43 | ADD: 2510 BROADWAY |
| CONT: JHAMTREE |
| TEL: (561)602-0009 |
| |
| FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| W/ 2009 FBC SUPPLEMENTS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 2007EXISTING BUILDING CODE LEVEL II 701.3 |
| COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| OF THE FLORIDA BUILDING CODE, BUILDING. |
| 2ND REVIEW |
| |
| 1A) COMPLIED. |
| |
| 1B) SEMI- COMPLIED. SHEET SP-1 INDICATES AN OCCUPANT |
| LOAD OF 52 OCCUPANTS, PLEASE REVIEW SECTION / TABLE |
| 1015.1 WHICH WILL REQUIRE (2) POINTS OF EGRESS, AND |
| THEY WILL TO MEET THE REQUIREMENT FOR 1/2 THE DIAGONAL |
| DISTANCE APART FBC-B 1015.2.1. |
| |
| 1C) THE PROPOSED DOOR# (02) IS LOCATED2.5 FEET FROM |
| THTE PROPERTY LINE SEE SP-1, PLEASE REVIEW FBC-B TABLE |
| 704.7 FOR ALLOWABLE OPENINGS, UNPROTECTED OR PROTECTED, |
| 0-5 FEET OPENINGS ARE NOT ALLOWED. |
| |
| 2-6) COMPLIED. |
| |
| 7) EVEN IF THE DESIGNEER OF RECORD PULL THE DOOR# 02 |
| BACK BEYOND THE 0-3' ALLOWING FOR PROTECTED OPENINGS |
| THE OTHER ISSUE WILL BE WITH THE EXIT DISCHARGE MEETING |
| THESE REQUIREMENTS: |
| |
| 2007/ 2009 FBC-B 1024.3 EXIT DISCHARGE LOCATION. |
| EXTERIOR BALCONIES, STAIRWAYS AND RAMPS SHALL BE |
| LOCATED AT LEAST 10 FEET (3048 MM) FROM ADJACENT LOT |
| LINES AND FROM OTHER BUILDINGS ON THE SAME LOT UNLESS |
| THE ADJACENT BUILDING EXTERIOR WALLS AND OPENINGS ARE |
| PROTECTED IN ACCORDANCE WITH SECTION 704 BASED ON FIRE |
| SEPARATION DISTANCE. |
| |
| 2007/ 2009 FBC-B 1024.4 EXIT DISCHARGE COMPONENTS. EXIT |
| DISCHARGE COMPONENTS SHALL BE SUFFICIENTLY OPEN TO THE |
| EXTERIOR SO AS TO MINIMIZE THE ACCUMULATION OF SMOKE |
| AND TOXIC GASES. |
| |
| 2007/ 2009 FBC-B 1024.5 EGRESS COURTS. EGRESS COURTS |
| SERVING AS A PORTION OF THE EXIT DISCHARGE IN THE MEANS |
| OF EGRESS SYSTEM SHALL COMPLY WITH THE REQUIREMENTS OF |
| SECTION 1024. |
| |
| 2007/ 2009 FBC-B 1024.5.1 WIDTH. THE WIDTH OF EGRESS |
| COURTS SHALL BE DETERMINED AS SPECIFIED IN SECTION |
| 1005.1, BUT SUCH WIDTH SHALL NOT BE LESS THAN 44 |
| INCHES. |
| |
| THE CONTRACTOR SUBMITTED A PRODUCT APPROVAL FOR DOOR # |
| 2 QUALITY ENGINEERED PRODUCT CO. INC. FOR WIND AND |
| LARGE MISSILE IMPACT BUT NO TESTING REPORT FOR THE FIRE |
| RATING OF DOOR, 2007/ 2009 FBC-B TABLE 715.4. |
| |
| 8) THE COVER SHEET INDICATES THE PREVIOUS TENANT TO BE |
| A AUTO REPAIR GARAGE MAKING THIS A S-1 OCCUPANCY. A |
| CHANGE IN OCCUPANCY REQUIRES IMPACT FEE REVIEW. BEFORE |
| A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT FEES MUST |
| BE PAID TO PALM BEACH COUNTY. THE ACTUAL PERMIT SET OF |
| PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY OF THE |
| PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION. PLEASE |
| CALL (561)233-5025 FOR MORE INFORMATION. |
| |
| JAMES A. WITMER C.B.O. |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| TEL: (561)805-6715 |
| FAX:(561)805-6731 |
| E-MAIL: [email protected] |
| |
| |
| |
| |